General settings
The following general settings define the general behavior of the function. These settings are static i.e.
it is not possible to change them by editing the setting group.
Table. 5.3.6 - 89. General settings of the function.
Name
Range
Default
Description
I0dir> LN
mode
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
1: On
Set mode of DEF block.
This parameter is visible only when
Allow setting of individual LN mode is enabled in
General menu.
U0
directional
phase
1: U0
2: -U0
1: U0
If the connected neutral voltage polarity is opposite to the connected residual current,
this parameter can swap the angle reference.
U0> Meas
input
select
1: Select
2: U0
Calculated
3: U3
Input
4: U4
Input
1:
Select
Defines which available neutral voltage measurement is used. Available neutral voltages
depend on measurement settings (
Measurements
→
Transformers
→
VT module).
Measured
magnitude
1: RMS
2: TRMS
3: Peak-
to-peak
1: RMS
Defines which available measured magnitude is used by the function. This parameter is
available when "Input selection" has been set to "I01" or "I02".
Input
selection
1: I01
2: I02
3: I0Calc
1: I01
Defines which measured residual current is used by the function.
Pick-up
The the pick-up of the I0dir> function is controlled by the
I0
set
setting parameter and the
U0
set
setting
parameter. The former defines the maximum allowed measured current, while the latter defines the
maximum allowed measured voltage and checks the angle difference before action from the function.
The function constantly calculates the ratio between the I0
set
and the
U0
set
and the measured
magnitudes (
I
m
and
U
m
). The reset ratio of 97 % is built into the function and is always relative to the
I0
set
(or
U0
set
) value. When the
I
m
exceeds the
I0
set
value it triggers the pick-up operation of the
function.
Table. 5.3.6 - 90. Pick-up settings.
Name
Description
Range
Step
Default
I0
set
Pick-up setting
0.005…40.00×I
n
0.001×I
n
1.20×I
n
U0
set
Pick-up setting
1…75%U
n
0.01%U
n
20%U
n
Grounding
type
Network grounding method
1: Unearthed
[32N Var]
2: Petersen coil
GND [32N Watt]
3: Grounded
[67N]
4: I0
Cos
& I0
Sin
broad range with
MCD [32N Var/
Watt]
-
1:
Unearthed
A
AQ
Q-C255
-C255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00035
101