![Arcteq AQ-C255 Скачать руководство пользователя страница 330](http://html1.mh-extra.com/html/arcteq/aq-c255/aq-c255_instruction-manual_2964905330.webp)
Name
Range
Step
Default
Description
Clear
newest
record
0: -
1: Clear
-
0: -
Clears the newest stored disturbance recording.
Clear
oldest
record
0: -
1: Clear
-
0: -
Clears the oldest stored disturbance recording.
Max.
number of
recordings
0…100
1
-
Displays the maximum number of recordings that can be stored in the
device's memory with settings currently in use. The maximum number
of recordings can go up to 100.
Max.
length of a
recording
0.000...1800.000s 0.001s -
Displays the maximum length of a single recording.
Max.
location of
the pre-
trigger
0.000...1800.000s 0.001s -
Displays the highest pre-triggering time that can be set with the
settings currently in use.
Recordings
in memory
0…100
1
-
Displays how many recordings are stored in the memory.
Table. 5.5.4 - 280. Recorder trigger setting.
Name
Description
Recorder
trigger
Selects the trigger input(s). Clicking the "Edit" button brings up a pop-up window, and checking the boxes
enable the selected triggers.
Table. 5.5.4 - 281. Recorder settings.
Name
Range
Step Default
Description
Recording length 0.100...1800.000s 0.01s 1s
Sets the length of a recording.
Recording mode
0: FIFO
1: Keep olds
-
0: FIFO
Selects what happens when the memory is full.
"FIFO" (= first in, first out) replaces the oldest stored recording
with the latest one. "Keep olds" does not accept new recordings.
Analog channel
samples
0: 64s/c
1: 32s/c
2: 16s/c
3: 8s/c
-
0: 64s/c
Selects the sample rate of the disturbance recorder in samples
per cycle. The samples are saved from the measured wave
according to this setting.
Digital channel
samples
5ms (fixed)
-
5
ms(fixed) The fixed sample rate of the recorded digital channels.
Pretriggering
time
0.2...30.0s
0.1s
0.2s
Sets the recording length before the trigger.
Analog recording
CH1...CH20
0…8 freely
selectable
channels
-
-
Selects the analog channel for recording. Please see the list of all
available analog channels in the section titled "Analog and digital
recording channels".
A
AQ
Q-C255
-C255
Instruction manual
Version: 2.06
328
© Arcteq Relays Ltd
IM00035