Name
Unit
Range
Step
Description
Voltage Ux
TRMS
("UxVolt TRMS
p.u.")
× U
n
0.00…500.0 0.01
The TRMS voltage (inc. harmonics up to 31
st
) measurement (in p.u.)
from each of the voltage channels.
Table. 5.2.2 - 25. Secondary voltage measurements.
Name
Unit
Range
Step
Description
Secondary voltage
Ux
("Ux Volt sec")
V
0.00…500.0 0.01
The secondary RMS voltage measurement from each of the voltage
channels.
Secondary voltage
Ux TRMS
("UxVolt TRMS
sec")
V
0.00…500.0 0.01
The secondary TRMS voltage (inc. harmonics up to 31
st
) measurement
from each of the voltage channels.
Table. 5.2.2 - 26. Voltage phase angle measurements.
Name
Unit
Range
Step
Description
Ux Angle
deg
0.00…360.00
0.01
The phase angle measurement from each of the four voltage inputs.
Table. 5.2.2 - 27. Per-unit sequence voltage measurements.
Name
Unit
Range
Step
Description
Positive sequence
voltage
("Pos.seq.Volt.p.u.")
× U
n
0.00…500.0 0.01
The measurement (in p.u.) from the calculated positive sequence
voltage.
Negative sequence
voltage
("Neg.seq.Volt.p.u.")
× U
n
0.00…500.0 0.01
The measurement (in p.u.) from the calculated negative sequence
voltage.
Zero sequence voltage
("Zero.seq.Volt.p.u.")
× U
n
0.00…500.0 0.01
The measurement (in p.u.) from the calculated zero sequence
voltage.
Table. 5.2.2 - 28. Primary sequence voltage measurements.
Name
Unit
Range
Step
Description
Primary positive sequence
voltage
("Pos.seq.Volt.pri")
V
0.00…1000000.00 0.01
The primary measurement from the calculated positive
sequence voltage.
Primary negative sequence
voltage
("Neg.seq.Volt.pri")
V
0.00…1000000.00 0.01
The primary measurement from the calculated negative
sequence voltage.
Primary zero sequence
voltage
("Zero.seq.Volt.pri")
V
0.00…1000000.00 0.01
The primary measurement from the calculated zero
sequence voltage.
Table. 5.2.2 - 29. Secondary sequence voltage measurements.
Name
Unit
Range
Step
Description
Secondary positive sequence
voltage
("Pos.seq.Volt.sec")
V
0.00…4800.0 0.01
The secondary measurement from the calculated positive
sequence voltage.
Secondary negative sequence
voltage
("Neg.seq.Volt.sec")
V
0.00…4800.0 0.01
The secondary measurement from the calculated negative
sequence voltage.
A
AQ
Q-C255
-C255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00035
37
Содержание AQ-C255
Страница 1: ...AQ C255 Capacitor bank protection IED Instruction manual ...
Страница 2: ......
Страница 363: ...Figure 7 4 180 Example block scheme A AQ Q C255 C255 Instruction manual Version 2 06 Arcteq Relays Ltd IM00035 361 ...
Страница 384: ...Figure 8 14 202 Device installation A AQ Q C255 C255 Instruction manual Version 2 06 382 Arcteq Relays Ltd IM00035 ...