6RL SERIES OPERATION MANUAL
SECTION 7: REMOTE PROGRAMMING
Entire Contents Copyright
2018 by Adaptive Power Systems, Inc. (APS) • All Rights Reserved • No reproduction without written authorization from APS.
6RL Series Regenerative DC Load Operation Manual
Page 138 of 204
Configuration (before start)
Nr.
Command
Description
1
00 05 01 92 FF 00 2D FA
Activate remote control
2
00 06 2E E1 00 03 91 04
Activate PV simulation mode DAYET
3
00 06 2E F0 00 00 81 00
Select technology: Manual (all required parameters must be
defined, here as with commands 4-10)
4
00 10 2F 02 00 02 04 3F 4C CC CD F7 ED
Fill factor voltage (FFU): 0,8
5
00 10 2F 04 00 02 04 3F 47 AE 14 EE FF
Fill factor current (FFI): 0,78
6
00 10 2F 06 00 02 04 39 9D 49 52 84 57
Temperature coefficient α for ISC: 0,0003 /°C
7
00 10 2F 08 00 02 04 BB 44 9B A6 A1 7F
Temperature coefficient β for UOC: -0,003 /°C
8
00 10 2F 0A 00 02 04 3D 94 7A E1 00 75
Scaling factor CU for UOC: 0,0725
9
00 10 2F 0C 00 02 04 39 66 AF CD 7F D1
Scaling factor CR for UOC: 0,00022 m²/W
10
00 10 2F 0E 00 02 04 3B 4E 70 3B A7 CE
Scaling factor CG for UOC: 0,00315 W/m²
11
00 05 2E F1 FF 00 D5 30
Select input mode: ULIK
12
00 06 2F 10 61 47 E8 A8
Set open circuit voltage: 38 V (=0x6147)
13
00 06 2F 11 08 6F 97 26
Set short-circuit current: 7 A
14
00 05 2E F2 FF 00 25 30
Activate data recording
15
00 05 2E E5 00 00 D4 C4
Deactivate interpolation of day trend data
Write day trend data (before the start)
Nr.
Command
Description
16
00 05 2E E6 FF 00 65 34
Select access mode: write
17
00 05 2E E7 FF 00 34 F4
Delete former data (should be executed every time
before loading new data)
18
00 10 2E EA 00 06 0C 00 00 00 01 44 44 66
66 00 00 01 F4 88 23
Write 1
st
day trend data set:
Irradiation: 500 W/m²
Temperature: 20°C Dwell time: 500 ms
19
00 10 2E EA 00 06 0C 00 00 00 02 6D 3A
74 0D 00 00 05 DC E4 C3
Write 2
nd
day trend data set:
Irradiation: 800 W/m²
Temperature: 28°C Dwell time: 1500 ms
...
Write further data sets, a total of 500
517
00 10 2E EA 00 06 0C 00 00 01 F4 A3 D6 7F FF
00 00 4E 20 34 AF
Write 500. day trend data set:
Irradiation: 1200 W/m²
Temperature: 35°C Dwell time: 20000 ms
Control, also during simulation run
Nr.
Command
Description
518
00 05 2E E6 FF 00 65 34
Start simulation -> the simulation will stop automatically after
the time that results from the total of dwell times in all
written data sets