SG Series Programming
SCPI Command Operation
M550129-03 Rev L
6-25
6.10
HTRIGGER SCPI COMMAND SUBSYSTEM
This section applies only to units with the External User Interface
(Currently only available on Ethernet versions).
The HTRIGGER function allows the user to apply an External User
Interface input signal to initiate a sequence or a voltage or current ramp.
Once a hardware trigger is run, Arm goes to 0 (not armed); however, the
last loaded sequence remains in memory.
6.10.1
HTRIGGER SCPI Command Summary
HTRIGger
:ABORt
:RAMP
:SEQuence
(Available only with SGI power supplies
– see Section 6.13.)
:SEQuence?
(Available only with SGI power supplies
– see Section 6.13.)
:ARM
(Available only with SGI power supplies
– see Section 6.13.)
:ARM?
(Available only with SGI power supplies
– see Section 6.13.)
6.10.2
HTRIGGER SCPI Command Reference
Command
Description
SCPI
HTRIGger
Hardware trigger subsystem.
N
:ABORt
Stops the execution of a currently running hardware trigger
function. In addition:
For Ramp: Clears all settings of voltage and current.
For Sequence: Sets the Arm function to 0 (not armed).
N
:RAMP
Executes voltage or current ramping function previously
programmed by the SOURce command, i.e.,
SOURce:VOLTage:RAMP
SOURce:CURRent:RAMP
N
:SEQuence
<string>
(SGI only); loads a Sequence to be initialized by the external
Hardware Trigger. This command must be followed by the
HTRIG:ARM command before the Hardware Trigger becomes
operational.
N
:SEQuence?
(SGI only); returns the currently loaded sequence name
N
:ARM <boolean>
(SGI only); readies the last loaded sequence to run when the
external Hardware Trigger signal is issued.
1 = Ready to run sequence when Hardware trigger is engaged.
0 = Not Armed, Hardware trigger is ignored
NOTE: To arm a different sequence, issue the HTRIG:SEQ
command first.
N
:ARM?
(SGI only); returns the ready status of the last loaded
sequence.
1 = Ready to run sequence when Hardware trigger is engaged.
0 = Not Armed, Hardware trigger is ignored
NOTE: To load a new sequence to be armed you must issue
the HTRIG:SEQ command first.
N
Содержание Sorensen SG Series
Страница 2: ......
Страница 4: ...Contents SG Series Programming viii M550129 03 Rev L This page intentionally left blank...
Страница 6: ...Contents SG Series Programming x M550129 03 Rev L This page intentionally left blank...
Страница 8: ...Contents SG Series Programming xii M550129 03 Rev L This page intentionally left blank...
Страница 14: ...Contents SG Series Programming xviii M550129 03 Rev L This page intentionally left blank...
Страница 16: ...Overview SG Series Programming 1 2 M550129 03 Rev L This page intentionally left blank...
Страница 126: ...SCPI Command Operation SG Series Programming 6 60 M550129 03 Rev L This page intentionally left blank...
Страница 143: ...M550129 03 Rev L 8 1 SECTION 8 SCPI STATUS IMPLEMENTATION...
Страница 144: ...SCPI Status Implementation SG Series Programming 8 2 M550129 03 Rev L This page intentionally left blank...
Страница 146: ...This page intentionally left blank...