Impulse™ Series
44
3.7.5 Configuration examples (Continued)
Figure 3.7-6
Note: When liquid level drops into Lower Dead Zone the output will
indicate the end of probe and will remain there until the level rises above
the Lower Dead Zone
Vessel Configuration:
• Level Units: Inches
• Tank Height: 120
• Sensor Offset: 6
• Volume Units Gallons
• Maximum Capacity 5000
• Vessel Type: Horizontal cylinder with dished ends
• LRV: 0
• URV: 4818
• Material Type: Oil
Note: When liquid level drops into Lower Dead Zone the output will
indicate the end of probe and will remain there until the level rises above
the Lower Dead Zone
.
Distance Configuration:
• Level Units: Inches
• Tank Height: 120
• LRV: (120 + 6 -110) = 16
• URV: (120 + 6) = 126: Enter 124. URV can not be set greater than
probe length
• Material Type: Oil
Note: When liquid level drops into Lower Dead Zone the output will
indicate the end of probe and will remain there until the level rises above
the Lower Dead Zone.
Содержание Impulse GW Series
Страница 4: ...Contents...
Страница 6: ...Section 1...
Страница 16: ...Section 2...
Страница 25: ...Installation 19 2 6 Dual Compartment Housing...
Страница 26: ...Section 3...
Страница 56: ...Section 4...
Страница 82: ...Impulse Series 76 5 2 1 System Dimensions Continued...
Страница 83: ...Supplementary ATEX Installation Instructions 77 5 2 1 System Dimensions Continued...
Страница 84: ...Impulse Series 78 5 2 1 System Dimensions Continued...
Страница 86: ...Section 6...
Страница 92: ...Section 7...
Страница 93: ...Control Drawings 87 Section 7 Control Drawings 7 1 FM FMC Control Drawings...
Страница 94: ...Impulse Series 88 7 1 FM FMC Control Drawings Continued...
Страница 95: ...Control Drawings 89 7 2 ATEX Control Drawings...
Страница 96: ...Impulse Series 90 7 2 ATEX Control Drawings Continued...