Configuration and Calibration
41
3.7.4
Configuration Parameters (Continued)
TDR Config
Configures the current output for Near Zone and Lost Echo
conditions
Lost Echo occurs when the unit cannot find a valid level or
the end of the probe and represents an error condition.
Near Zone occurs when a level is tracked into the Upper
Dead Zone. When this occurs the current will go to the
selected value and remain there until the level falls back
into the measurable range
NOTE: If the system is powered on or “signal acquire” is
activated with the level in the Near Zone, it will not be
detected and an erroneous reading may result.
Lost Echo:
Low Current (3.7
mA - Default)
High Current (22
mA)
Near Zone:
Low Current (3.7
mA)
High Current (22
mA - Default)
Strapping
Table
The strapping table is a look-up table of level vs. volume
that is entered by the user based on known parameters.
Use this function for volume measurement only.
User editable values
View Signals Opens “Tank Profile Data” window to display a graph of
the active signal
File Menu
Open
Open saved HRTWin file
Close
Close current transmitter configuration leaving HRTWin
open
Save (Ctrl+S) Save current HRTWin configuration to a file
Enter “file name”.
TDR
Print Setup
Standard Windows print setup functions
Print (Ctrl+P) Print current HRTWin configuration to a file.
Optionally select to print Strapping Table and/or Real
Time View.
Cancel
Check boxes to print
Strapping Table
and/or Real Time
View
Exit (F9)
Close HRTWin
Field Device Menu
Read from
transmitter
(F3)
Downloads configuration data from the electronic unit to
the computer
Real Time
View (F4)
Opens window to display current level and distance
measurements and status
Write to
transmitter
(F5)
Uploads changes from the computer to the electronic unit.
Содержание Impulse GW Series
Страница 4: ...Contents...
Страница 6: ...Section 1...
Страница 16: ...Section 2...
Страница 25: ...Installation 19 2 6 Dual Compartment Housing...
Страница 26: ...Section 3...
Страница 56: ...Section 4...
Страница 82: ...Impulse Series 76 5 2 1 System Dimensions Continued...
Страница 83: ...Supplementary ATEX Installation Instructions 77 5 2 1 System Dimensions Continued...
Страница 84: ...Impulse Series 78 5 2 1 System Dimensions Continued...
Страница 86: ...Section 6...
Страница 92: ...Section 7...
Страница 93: ...Control Drawings 87 Section 7 Control Drawings 7 1 FM FMC Control Drawings...
Страница 94: ...Impulse Series 88 7 1 FM FMC Control Drawings Continued...
Страница 95: ...Control Drawings 89 7 2 ATEX Control Drawings...
Страница 96: ...Impulse Series 90 7 2 ATEX Control Drawings Continued...