RS1500000 Rev. 2
22
Component Testing
To avoid risk electrical shock, personal injury, or death,
always disconnect electrical power source to the freezer
before attempting to service, unless test procedures require
power to be connected. When removing any wiring from terminals they must be replaced on the same terminals.
Ensure all ground wires are connected before certifying unit as repaired and/or operational.
WARNING
!
Performance Data at Control Setting # 4
Manual Defrost
Capacity
Cu. Ft.
Insulation
Type
Amb
Wattage
%
Running
High
Side
Low
Side
Amps
Running
Capacitor
11.7
Foam
70
°
90
°
110
°
90
−
110
95
−
115
100
−
120
35
−
45
50
−
60
80
−
90
95
−
115
125
−
145
170
−
190
−
5
−
3
−
4
−
2
−
2 0
0.7
−
1.0
0.8
−
1.1
0.8
−
1.1
12 uF
210 V
15.2
Foam
70
°
90
°
110
°
95
−
115
100
−
120
105
−
125
35
−
45
55
−
65
90
−
100
95
−
115
125
−
145
165
−
185
−
4
−
2
−
3
−
1
−
3
−
1
0.9
−
1.2
0.9
−
1.2
1.0
−
1.3
12 uF
210 V
16.9
Foam
70
°
90
°
110
°
105
−
125
110
−
130
115
−
135
40
−
50
55
−
65
90
−
100
95
−
115
130
−
150
165
−
185
−
4
−
2
−
3
−
1
−
2 1
0.9
−
1.2
0.9
−
1.2
1.0
−
1.3
12 uF
210 V
19.7
Foam
70
°
90
°
110
°
120
−
140
125
−
145
130
−
150
40
−
50
55
−
65
90
−
100
100
−
120
135
−
155
175
−
195
−
4
−
2
−
3
−
1
−
1
−
1
1.0
−
1.3
1.0
−
1.3
1.2
−
1.5
12 uF
210 V
Performance Data at Control Setting # 4
Auto Defrost
15.0
Foam
70
°
90
°
110
°
125
−
145
130
−
150
135
−
155
45
−
55
60
−
70
90
−
100
105
−
125
140
−
160
185
−
205
−
3
−
1
−
3
−
1
−
1 1
1.0
−
1.3
1.1
−
1.4
1.2
−
1.5
12 uF
210 V
16.7
Foam
70
°
90
°
110
°
135
−
155
140
−
160
145
−
165
35
−
45
45
−
55
90
−
100
100
−
120
135
−
155
175
−
195
−
3
−
1
−
2 0
−
2 0
1.2
−
1.5
1.2
−
1.5
1.2
−
1.6
12 uF
210 V
19.6
Foam
70
°
90
°
110
°
135
−
155
140
−
160
145
−
165
40
−
50
60
−
70
90
−
100
95
−
115
130
−
150
175
−
195
−
4
−
2
−
4
−
2
−
2 0
1.2
−
1.5
1.2
−
1.5
1.3
−
1.6
12 uF
210 V