SERVICE MANUAL
R5888C
QUADRAMHO
Chapter 2
Page 19 of 74
At the end of the loop these output registers are then output via the appropriate
output ports.
The above is true when the standards scheme options are selected. If an invalid
scheme or a test option is selected then only parts of the main loop are run, see
Section 4.9.46.
Most of the software timers are not run in the main loop, but in the timer interrupt
routine. (This is described later on in this section).
During normal scheme operation the loop time (time taken to travel once round the
loop) including the servicing of the timer interrupt is approximately 3.1 – 3.8ms
depending on the scheme selected. The exception to this is when a Zone 1
interrupt takes place. The loop time will also change if a test option or invalid
scheme is selected.
4.9.26 Z1 NT subroutine
This feature is present to speed up tripping when a Zone 1 fault is detected.
This feature uses the microcontroller external interrupt, which is driven by the
Zone 1 comparator outputs gated with the low set current level detectors and high
set neutral level detector.
After an interrupt has taken place, the Z1 INT routine is entered; interrupt is
disabled to prevent another interrupt occurring until after the present one has
finished, also a flag is set to indicate that an interrupt has taken place. If any main
loop trip is in progress or the SOTF feature is enabled, the interrupt will return to
the main loop. The main program will be run from the point when the interrupt
occurred (see timer interrupt section). If the SOTF feature is not enabled and no
main loop trip is in progress then when the interrupt routine has been completed,
the microcontroller executes the FTRIP routine.
4.9.27 FTRIP subroutine
The FTRIP routine reads the Zone 1 comparators and performs level detector checks
on these. If no fault (after level detector checks) is present then the software is
executed from the beginning of the main loop. If a fault is present the following
then occurs:
a) Fault locator outputs are set.
b) Hysteresis is sent.
c) Correct tripping contacts are closed (see tripping logic Section 5.16.31).
d) Carrier is transmitted if PUR scheme is selected.
e) The trip drop off timer is run.
After the above the software is executed from the beginning of the main loop.
4.9.28 LOAD subroutine
The LOAD routine performs the following:
Firstly the code switch number (CSN) and the code switch number override
(CSN O/R) (pins 1 to 8 of socket 1) are stored in two registers. The CSN O/R is
tested to determine if an override is required. If an override is required then the
CSN O/R will determine which scheme is run. If no override is required then the
CSN will determine the scheme. The CSN or CSN O/R is then tested to see if a
valid scheme option is selected (00–09). If this is not true, then the test option
software is run (See Section 4.9.46).
Содержание SHPM 101
Страница 1: ...Service Manual Quadramho Distance Protection Type SHPM 101...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 13: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 1 Application...
Страница 14: ......
Страница 44: ......
Страница 55: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 2 Description Technical Data...
Страница 56: ......
Страница 137: ...SERVICE MANUAL R5888C QUADRAMHO Chapter 2 Appendix A Page 1 of 71 Figure 1 Quadramho Quiet area Interface area...
Страница 208: ......
Страница 209: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 3 Electronic Module Housing...
Страница 210: ......
Страница 211: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 4 Installation...
Страница 212: ......
Страница 214: ......
Страница 216: ......
Страница 217: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 5 Commissioning Instructions...
Страница 218: ......
Страница 262: ...SERVICE MANUAL R5888B QUADRAMHO Chapter 5 Appendix A Page 18 of 18 Figure 11c LAG LEAD VA VC VB 0 90 270 180...
Страница 266: ......
Страница 280: ......
Страница 282: ......
Страница 285: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 6 Problem Analysis...
Страница 286: ......
Страница 288: ......
Страница 310: ...SERVICE MANUAL R5888B QUADRAMHO Chapter 6 Addendum A Page 10 of 15 Figure 6 Lenticular characteristic X R 80...
Страница 316: ......
Страница 317: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 7 Relay Identification...
Страница 318: ......
Страница 320: ......
Страница 323: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 8 Special Variations...
Страница 324: ......
Страница 326: ......
Страница 332: ......
Страница 335: ......