SERVICE MANUAL
R5888B
QUADRAMHO
Chapter 1
Page 7 of 27
For ground faults on multiple-earthed systems, it is possible, due to healthy phase
current levels, for the magnitude of the greatest phase difference current to be
larger than the neutral current at the relaying point. It is extremely unlikely,
however, for the ratio of these two currents to exceed the level of 10, which would
need to be reached before the low-set neutral detector failed to operate for a
ground fault.
Section 15.
SELECTION OF SCHEME LOGIC PROGRAMS
The distance scheme logic programs are selected by setting two coded selector
switches to a particular two-digit number. A list of scheme codings is given in
Chapter 2.
Section 16.
SETTING OF SCHEME OPTION SWITCHES
SW1
(LEFT)
SOTF tripping initiated by comparators
(RIGHT)
SOTF tripping initiated by level detectors
SW2
(LEFT)
SOTF enable time = 110s
(RIGHT)
SOTF enable time = 200ms
SW3
(LEFT)
VTS indicates only
(RIGHT)
VTS indicates and blocks relay
SW4
(LEFT)
Normal block autoreclose action
(RIGHT)
Block autoreclose also for Z1 and aided trip 3 phase faults
SW5
(LEFT)
Self checking feature disabled
(RIGHT)
Self checking feature enabled
SW6
(LEFT)
Normal block autoreclose
(RIGHT)
Block autoreclose also for signalling channel out of service
SW7
(LEFT)
Disable trip by weak infeed feature
(RIGHT)
Enable trip by weak infeed feature
SW8
(LEFT)
POR weak infeed feature disabled
(RIGHT)
POR weak infeed feature enabled
SW9
(LEFT)
Power swing blocking function disabled
(RIGHT)
Power swing blocking function enabled
Section 17.
DISCUSSION ON APPLICATION OF VARIOUS DISTANCE
SCHEME OPTIONS
17.1
Basic (see Figure 3)
• This scheme does not require signalling channels.
• A major disadvantage is that not all the faults within a protected section
can be cleared instantaneously by distance relays at both ends.
• Scheme is suitable for a single circuit radial line where a distance relay
would be used at the source end only.
Содержание SHPM 101
Страница 1: ...Service Manual Quadramho Distance Protection Type SHPM 101...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 13: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 1 Application...
Страница 14: ......
Страница 44: ......
Страница 55: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 2 Description Technical Data...
Страница 56: ......
Страница 137: ...SERVICE MANUAL R5888C QUADRAMHO Chapter 2 Appendix A Page 1 of 71 Figure 1 Quadramho Quiet area Interface area...
Страница 208: ......
Страница 209: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 3 Electronic Module Housing...
Страница 210: ......
Страница 211: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 4 Installation...
Страница 212: ......
Страница 214: ......
Страница 216: ......
Страница 217: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 5 Commissioning Instructions...
Страница 218: ......
Страница 262: ...SERVICE MANUAL R5888B QUADRAMHO Chapter 5 Appendix A Page 18 of 18 Figure 11c LAG LEAD VA VC VB 0 90 270 180...
Страница 266: ......
Страница 280: ......
Страница 282: ......
Страница 285: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 6 Problem Analysis...
Страница 286: ......
Страница 288: ......
Страница 310: ...SERVICE MANUAL R5888B QUADRAMHO Chapter 6 Addendum A Page 10 of 15 Figure 6 Lenticular characteristic X R 80...
Страница 316: ......
Страница 317: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 7 Relay Identification...
Страница 318: ......
Страница 320: ......
Страница 323: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 8 Special Variations...
Страница 324: ......
Страница 326: ......
Страница 332: ......
Страница 335: ......