SERVICE MANUAL
R5888B
QUADRAMHO
Chapter 1
Page 18 of 27
Ground loop impedance to Zone 1 reach point
= 2 x (1.37 + j3.76) + (5.99 + j14.8)
3
= (2.91 + j7.44) = 7.99 /68.6
°
Source to fault ground loop impedance
= (11.34 + j36.87) + (2.91 + j7.44)
= (14.25 + j44.31) = 46.55 /72.2
°
Relay voltage for a ground fault at the Zone 1
Reach point
= 7.99
x 63.5 = 10.91 volts
46.55
For
±
5% reach accuracy with the Zone 1 multiplier set to unity Quadramho
requires at least 2.05 volts for the ground fault measurement or at least 3.55 volts
for phase fault measurement. For
±
10% accuracy the required voltages are 1.04
and 1.8 volts respectively. For Zone 1 multipliers greater than unity, the required
relay voltages for accuracy vary linearly with the multiplier setting.
In this, the Zone 1 multiplier = 1.04. Thus the required voltages for
±
5% reach
accuracy are:
1.04 x 2.05 = 2.13 volts for ground faults
1.04 x 3.55 = 3.69 volts for phase faults
Both voltage requirements are met in this application.
19.10
Checking relay current sensitivity for faults at the Zone 3 reach point
The worst case will be for an ground fault at the Zone 3 reach point.
Maximum source ground loop impedance behind relay.
= 38.6 /72.9
°
= (11.35 + j36.9)
Relay Zone 3 earth fault setting
= (Z
Ph
+ Z
N
) x Z3 multiplier
= (1.4 + 1.4) /70
°
x 4.6
= 2.58 /70
°
ohms secondary
5
5
= 35.3 /70
°
ohms primary
= (12.1 + j33.2) ohms primary
Overall source to fault ground loop impedance (including 40 ohms fault resistance)
= (11.35 + j36.9) + (12 .1 + j33.2) +40
= (63.5 + j70.1) ohms
= 94.6 /47.8
°
Current for a fault at the Zone 3 reach point
=
60 x 10
3
3 x 94.6
= 366A = 183% of CT rating (200/5A)
Relay current level detector sensitivities =
Z
Ph
Z
Ph
max x base level
Содержание SHPM 101
Страница 1: ...Service Manual Quadramho Distance Protection Type SHPM 101...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 13: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 1 Application...
Страница 14: ......
Страница 44: ......
Страница 55: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 2 Description Technical Data...
Страница 56: ......
Страница 137: ...SERVICE MANUAL R5888C QUADRAMHO Chapter 2 Appendix A Page 1 of 71 Figure 1 Quadramho Quiet area Interface area...
Страница 208: ......
Страница 209: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 3 Electronic Module Housing...
Страница 210: ......
Страница 211: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 4 Installation...
Страница 212: ......
Страница 214: ......
Страница 216: ......
Страница 217: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 5 Commissioning Instructions...
Страница 218: ......
Страница 262: ...SERVICE MANUAL R5888B QUADRAMHO Chapter 5 Appendix A Page 18 of 18 Figure 11c LAG LEAD VA VC VB 0 90 270 180...
Страница 266: ......
Страница 280: ......
Страница 282: ......
Страница 285: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 6 Problem Analysis...
Страница 286: ......
Страница 288: ......
Страница 310: ...SERVICE MANUAL R5888B QUADRAMHO Chapter 6 Addendum A Page 10 of 15 Figure 6 Lenticular characteristic X R 80...
Страница 316: ......
Страница 317: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 7 Relay Identification...
Страница 318: ......
Страница 320: ......
Страница 323: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 8 Special Variations...
Страница 324: ......
Страница 326: ......
Страница 332: ......
Страница 335: ......