SERVICE MANUAL
R5888B
QUADRAMHO
Chapter 1
Page 23 of 27
19.17
Selecting Zone 3 Reach
Blocking scheme is to be used so reverse Zone 3 reach should be set to Zone 2
reach of remote end relay (at MARCH 132 substation).
Zone 2 reach of remote end relay would be:
= MARCH – FEB line imp 50% (FEB – JAN line impedance)
= 60 x 0.44 /69
°
+ 0.5 x 20 x 0.44 /69
°
= 30.8 /69
°
ohms primary
Thus required Zone 3 reverse reach = 30.8 /69
°
ohms primary
= 12.84 /69
°
ohms secondary
Required Zone 3 reverse reach multiplier
= required reverse reach
|Z
Ph
|
= 12.84 = 2.68
4.8
Select K35 = 2
K36 = 0.7
K33 = 1
K37 = 1.0
Actual Zone 3 reverse reach
= (K35 + K36) K33 x K37 x Z
Ph
= 2.7 x 1 x 1 x 4.8 /70
°
= 12.96 /70
°
ohms secondary
Required Zone 3 forward reach = minimum possible if power swing blocking is
not required
Select K31 = 1
K32 = 0.0
Actual Zone 3 forward reach
= (K31 + K32) x K33 x Z
Ph
= 1.0 x 1 x 4.8 /70
°
= 4.8 /70
°
ohms secondary
Alternatively if power swing blocking is required, the required Zone 3 forward
reach
≥
120% of Zone 2 forward reach. Use of the Zone 3 lenticular settings may
be required to prevent load impedance encroaching on the Zone 3 and power
swing blocking impedance characteristics.
19.18
Ground fault compensation settings
Ground loop impedance of line Z
LE
= (1+K
N)
Z
L1
where K
N
=
Z
L0
– Z
L1
3Z
L1
Neutral impedance coarse setting = Z
N
= K
N
Z
Ph
Z
LO
– Z
L1
= (0.34 + j1.03) – (0.16 + j0.41)
= (0.18 + j0.62) = 0.65 /73.8
°
K
N
= 0.65 /73.8
°
= 0.492 /4.8
°
(49% compensation)
3 x 0.44 /69
°
Содержание SHPM 101
Страница 1: ...Service Manual Quadramho Distance Protection Type SHPM 101...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 13: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 1 Application...
Страница 14: ......
Страница 44: ......
Страница 55: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 2 Description Technical Data...
Страница 56: ......
Страница 137: ...SERVICE MANUAL R5888C QUADRAMHO Chapter 2 Appendix A Page 1 of 71 Figure 1 Quadramho Quiet area Interface area...
Страница 208: ......
Страница 209: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 3 Electronic Module Housing...
Страница 210: ......
Страница 211: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 4 Installation...
Страница 212: ......
Страница 214: ......
Страница 216: ......
Страница 217: ...Quadramho Distance Protection Type SHPM101 Service Manual Chapter 5 Commissioning Instructions...
Страница 218: ......
Страница 262: ...SERVICE MANUAL R5888B QUADRAMHO Chapter 5 Appendix A Page 18 of 18 Figure 11c LAG LEAD VA VC VB 0 90 270 180...
Страница 266: ......
Страница 280: ......
Страница 282: ......
Страница 285: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 6 Problem Analysis...
Страница 286: ......
Страница 288: ......
Страница 310: ...SERVICE MANUAL R5888B QUADRAMHO Chapter 6 Addendum A Page 10 of 15 Figure 6 Lenticular characteristic X R 80...
Страница 316: ......
Страница 317: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 7 Relay Identification...
Страница 318: ......
Страница 320: ......
Страница 323: ...Quadramho Distance Protection Type SHPM 101 Service Manual Chapter 8 Special Variations...
Страница 324: ......
Страница 326: ......
Страница 332: ......
Страница 335: ......