H38x/EN GL/D11
Global Documentation
Page 32/53
DS Agile H38x
4.6.4.4
Voltage dip immunity
Standard: EN 60255-11 / IEC 61000-4-11
Application mode
Group under test
Test level
AC
Power supply
40% Un @200ms (dip 60%) & 70% Un
@ 500ms (dip 30%) & 20% Un @ 5s (dip
20%)
4.6.4.5
Voltage interruptions immunity
Standard: IEC 60255-11
Application mode
Group under test
Test level
AC
Power supply
No loss : 10ms ; 20ms
Temporary loss : 50ms ; 100ms ; 200ms
; 500ms ; 5s
4.6.5 Atmospheric
4.6.5.1
Cold immunity
Standard: IEC 61850-3
/ IEEE 1613/ IEC 60870-2-2 / IEC 60068-2-1
Application mode
Group under test
Test level
Energised
Housing
Test Ab : -25°C ; 96h
Not energised
Housing
Test Ad : -40°C ; 96h
4.6.5.2
Dry heat immunity
Standard: IEC 61850-3/ IEEE 1613
/ IEC 60870-2-2 / IEC 60068-2-2
Application mode
Group under test
Test level
Energised
Housing
Test Bd : +55°C ; 96h & +70°C ; 24h
Energised
Housing
Test Bd : +55°C ; 20d
Not energised
Housing
Test Bd : +85°C ; 96h
4.6.5.3
Damp heat immunity
Standard: IEC 61850-3
/ IEEE 1613/ IEC 60870-2-2 / IEC 60068-2-3 / IEC 60068-2-78
Application mode
Group under test
Test level
Energised
Housing
Test Ca : +40°C ; 10d ; 93%RH
4.6.5.4
Cyclic temperature with humidity immunity
Standard: IEC 61850-3
/ IEEE 1613/ IEC 61131-2
/ IEC 60870-2-2 / IEC 60068-2-30
Application mode
Group under test
Test level
Not energised
Housing
Test Db : Variant 2 ; +55°C ; 2 cycles (12h +
12h) ; RH = 93%
4.6.5.5
Barometric pressure immunity
Standard: IEC 61850-3
/ IEC 60870-2-2