H38x/EN GL/D11
Global Documentation
Page 26/53
DS Agile H38x
800MHz to 960MHz & 30 V/m
@ 1kHz 80% am ; 1.4GHz to
6GHz
NA
Power supply
NA
NA
Alarm contact
NA
NA
Earth connector
NA
NA
Copper Ethernet port
NA
NA
IRIG-B connector
NA
Standard: IEC 61850-3/ IEEE 1613/ ANSI/IEEE C37.90.2
Application mode
Group under test
Test level
NA
Housing
- 35V/m @ 1KHz 80%am ; 80MHz to 1GHz
- 35V/m @ pulse modulated 100%
- 35V/m @ 200Hz, pulse modulated 50% ; spot
tests at 80MHz, 160MHz, 450MHz, 900MHz and
900MHz
NA
Power supply
NA
NA
Alarm contact
NA
NA
Earth connector
NA
NA
Copper Ethernet port
NA
NA
IRIG-B connector
NA
4.6.2.3
Electrical Fast Transient/Burst immunity
Standard : IEC 61850-3 /
EN 61000-4-4
Application mode
Group under test
Test level
CM
Housing
NA
CM
Power supply
Class 4 : ± 4kV ; 5kHz or 100kHz
CM
Alarm contact
Class 4 : ± 4kV ; 5kHz or 100kHz ; coupling
clamp
CM
Earth connector
Class 4 : ± 4kV ; 5kHz or 100kHz
CM
Copper Ethernet port
Class 4 : ± 2kV ; 5kHz or 100kHz ; coupling
clamp
CM
IRIG-B connector
Class 4 : ± 2kV ; 5kHz or 100kHz ; coupling
clamp
Standard : IEEE 1613/ ANSI/IEEE C37.90.1
Application mode
Group under test
Test level
CM
Housing
NA
CM
Power supply
Class 4 : ± 4kV ; 2,5kHz
CM
Alarm contact
Class 4 : ± 4kV ; 2,5kHz
CM
Earth connector
Class 4 : ± 4kV ; 2,5kHz
CM
Copper Ethernet port
Class 4 : ± 4kV ; 2,5kHz
CM
IRIG-B connector
Class 4 : ± 4kV ; 2,5kHz