Global Documentation
H38x/EN GL/D11
DS Agile H38x
Page 27/53
4.6.2.4
Surge Immunity
Standard: IEC 61850-3
/ EN 61000-4-5
Application
mode
Group under test
Test level
CM
Housing
NA
CM
Power supply
Class 4 : ± 4kV ; 12
Ω
CM
Alarm contact
Class 4 : ± 4kV ; 42
Ω
CM
Earth connector
NA
CM
Copper Ethernet port
Class 4 : ± 4kV ; 2
Ω
CM
IRIG-B connector
Class 4 : ± 4kV ; 2
Ω
DM
Housing
NA
DM
Power supply
Class 4 : ± 2kV ; 2
Ω
DM
Alarm contact
Class 4 : ± 2kV ; 42
Ω
DM
Earth connector
NA
DM
Copper Ethernet port
NA
DM
IRIG-B connector
NA
4.6.2.5
Conducted disturbances immunity, induced by radio-frequency fields
Standard: IEC 61850-3
/ EN 61000-4-6
Application
mode
Group under test
Test level
NA
Housing
NA
NA
Power supply
Class 3 : 10V @ 1kHz 80%am ; 150kHz to
80MHz
NA
Alarm contact
Class 3 : 10V @ 1kHz 80%am ; 150kHz to
80MHz
NA
Earth connector
Class 3 : 10V @ 1kHz 80%am ; 150kHz to
80MHz
NA
Copper Ethernet port
Class 3 : 10V @ 1kHz 80%am ; 150kHz to
80MHz
NA
IRIG-B connector
Class 3 : 10V @ 1kHz 80%am ; 150kHz to
80MHz
4.6.2.6
Power frequency magnetic field immunity
Standard: IEC 61850-3/ EN 61000-4-8
Application
mode
Group under test
Test level
NA
Housing
Class 5 : 100/Am ; 1min & 1000A/m ; 3s
NA
Power supply
NA
NA
Alarm contact
NA
NA
Earth connector
NA
NA
Copper Ethernet port
NA
Содержание DS Agile H38 Series