H38x/EN GL/D11
Global Documentation
Page 28/53
DS Agile H38x
NA
IRIG-B connector
NA
4.6.2.7
Pulse magnetic field immunity
Standard: EN 61000-4-9
Application mode
Group under test
Test level
NA
Housing
Class 5 : 1000A/m
NA
Power
supply
NA
NA
Alarm contact
NA
NA
Earth connector
NA
NA
Copper Ethernet port
NA
NA
IRIG-B connector
NA
4.6.2.8
Damped oscillatory magnetic field immunity
Standard: IEC 61850-3/ EN 61000-4-10
Application mode
Group under test
Test level
NA
Housing
Class 5 : 100A/m ; 100KHz & 100A/m ; 1MHz
NA
Power
supply
NA
NA
Alarm contact
NA
NA
Earth connector
NA
NA
Copper Ethernet port
NA
NA
IRIG-B connector
NA
4.6.2.9
Conducted immunity, common mode disturbance
Standard: IEC 61850-3
/ EN 61000-4-16
Application mode
Group under test
Test level
CM
Housing
NA
CM
Power supply
Class 4 : 30V continuous disturbance &
300V short duration disturbance
CM
Alarm contact
Class 4 : 30V continuous disturbance &
300V short duration disturbance
CM
Earth connector
NA
CM
Copper Ethernet port
Class 4 : 30V continuous disturbance &
300V short duration disturbance
CM
IRIG-B connector
Class 4 : 30V continuous disturbance &
300V short duration disturbance
4.6.2.10 Damped oscillatory wave immunity
Standard: IEC 61850-3
/ IEEE 1613
/ ANSI/IEEE C37.90.1 / EN 61000-4-18
Application
mode
Group under test
Test level
CM
Housing
NA
CM
Power supply
Slow damped oscillatory wave, Class 3 : ± 2,5kV ;