Global Documentation
H38x/EN GL/D11
DS Agile H38x
Page 31/53
4.6.3.6
Fast shut-down/start-up immunity
Standard: IEC 61131-2
Application mode
Group under test
Test level
DC
Power supply
3 cycles : 5s shut-down ramp ; 5s start-
up ramp ; 1 to 5s @ Un
4.6.3.7
Reversal of DC power supply polarity immunity
Standard: IEC 60255-11
Application mode
Group under test
Test level
DC
Power supply
Reverse polarity ; 1min
4.6.3.8
Inrush current limits
Standard: None
Application mode
Group under test
Test level
DC
Power supply:
i < 20A @ t < 1,5 ms
i < 10A @ 1.5 ms
≤
t < 500 ms
i < 1,2 In @ t
≥
500 ms
4.6.3.9
Input current waveform limits
Standard: None
Application mode
Group under test
Test level
DC
Power supply
i peak to peak < 10% In
4.6.4
AC auxiliary power supply
4.6.4.1
Voltage variations immunity
Standard: IEC 61850-3
/ IEEE 1613
/ IEC 60870-2-1 / IEC 61131-2
/ IEC 60255-6
Application mode
Group under test
Test level
AC
Power supply
Nominal range of voltage : -20% &
+20%
AC
Power supply
Nominal range of frequency : -10% to
+10%
4.6.4.2
Harmonic immunity
Standard: IEC 61850-3
/ IEC 60870-2-1
Application mode
Group under test
Test level
AC
Power supply
Class H2 :
≤
10%
4.6.4.3
Third harmonic immunity on AC input
Standard: IEC 61131-2
Application mode
Group under test
Test level
AC
Power supply
10% Un ; 0° phase angle & 10% Un ;
180° phase angle