Global Documentation
H38x/EN GL/D11
DS Agile H38x
Page 25/53
CM Earth
connector
NA
CM
Copper Ethernet port
2kV
CM IRIG-B
connector
5kV
DM Housing
NA
DM Power
supply
3kV
DM Alarm
contact
3kV
DM Earth
connector
NA
DM
Copper Ethernet port
NA
DM IRIG-B
connector
3kV
4.6.1.4
Earthing continuity
Standard: IEC 61131-2
Application mode
Group under test
Test level
NA
Housing
Resistance
< 0,1
Ω
; I = 30A ; 2min
NA
Power supply
NA
NA
Alarm contact
NA
NA
Earth connector Resistance
< 0,1
Ω
; I = 30A ; 2min
NA
Copper Ethernet port
NA
NA
IRIG-B connector
NA
4.6.2 Electromagnetic
compatibility
4.6.2.1
Electrostatic Discharge
Standard: IEEE 1613 / ANSI/IEEE C37.90.3
Application mode
Group under test
Test level
NA
Housing
Class 4 : ± 8kV contact
discharge ; ± 15kV air
discharge
NA
Power supply
NA
NA
Alarm contact
NA
NA
Earth connector
NA
NA
Copper Ethernet port
NA
NA
IRIG-B connector
NA
4.6.2.2
Radiated immunity
Standard: IEC 61850-3
/ EN 61000-4-3
Application mode
Group under test
Test level
NA
Housing
Radiated immunity, Class 4 :
- 30V/m @ 1kHz 80%am ;
80MHz to 1GHz
- Radiated immunity from
digital radio telephones, Class
4 : 30V/m @ 1kHz 80% am ;
Содержание DS Agile H38 Series