H38x/EN GL/D11 

 
 

Содержание DS Agile H38 Series

Страница 1: ...DS Agile H38x Global Documentation H38x EN GL D11...

Страница 2: ......

Страница 3: ...Documentation CONTENTS 1 INTRODUCTION 2 SAFETY AND HANDLING 3 FUNCTIONAL DESCRIPTION 4 TECHNICAL DATA 5 INSTALLATION 6 MAKING CONNECTIONS TO THIS PRODUCT 7 MAINTENANCE 8 CONFIGURATION SETTINGS 9 APPL...

Страница 4: ...questions or specific problems do not take any action without proper authorization Please contact the appropriate Alstom technical sales office and request the necessary information Refer to the Syst...

Страница 5: ...0 2 6 Handling of Electronic Equipment 10 2 7 Packing and Unpacking 11 2 8 Guarantees 11 2 9 Copyrights Trademarks 12 2 9 1 Copyrights 12 2 9 2 Trademarks 12 2 9 3 Warnings regarding use of Alstom pro...

Страница 6: ...ntal Characteristics 23 4 6 1 Dielectric impulse and insulation 23 4 6 2 Electromagnetic compatibility 25 4 6 3 DC auxiliary power supply 30 4 6 4 AC auxiliary power supply 31 4 6 5 Atmospheric 32 4 6...

Страница 7: ...dministrator password 43 8 2 2 Setting the user password 43 8 2 3 Setting the SNMP V3 Administrator Password 43 8 2 4 Setting the SNMP V3 Operator Password 43 8 3 Configuration commands 44 8 4 Managem...

Страница 8: ...SHOWING LED POSITION 20 FIGURE 6 TYPICAL TELNET CONNECTION 21 FIGURE 7 H38X DIN RAIL MOUNTING DETAILS 35 FIGURE 8 H38X CONNECTION POINTS 36 FIGURE 9 EARTHING CABLE EXAMPLE 37 FIGURE 10 POWER SUPPLY W...

Страница 9: ...eds Standard Ethernet products rarely meet the constraints of electrical plants environmental power supply redundancy etc The new MiCOM DS Agile Hxxx series has been specifically tailored to respond t...

Страница 10: ...tches that are easy to install and operate They are designed to work in an electrical plant environment where standards such as IEC 61000 4 IEC 60255 5 apply The switch allows up to three devices end...

Страница 11: ...dangerous voltages will be present in certain parts of the equipment Failure to observe warning notices incorrect use or improper use may endanger personnel and equipment and also cause personal inju...

Страница 12: ...equipment is electrically isolated Any disassembly of the equipment may expose parts at hazardous voltage also electronic parts may be damaged if suitable electrostatic voltage discharge ESD precauti...

Страница 13: ...odules and PCB cards must not be inserted into or withdrawn from the equipment whilst it is energized since this may result in damage Fibre optic communication Where fibre optic communication devices...

Страница 14: ...eference to safety Altitude Operation up to 2000m standards EN 60950 1 2006 2 6 Handling of Electronic Equipment A person s normal movements can easily generate electrostatic potentials of several tho...

Страница 15: ...eplace software media that do not execute programming instructions if Alstom receive notice of such defects during the warranty period Alstom does not guarantee that the operation of the software shal...

Страница 16: ...ity suitability of compilers and development software used to develop an application installation errors software and hardware compatibility problems malfunctions or failures of electronic monitoring...

Страница 17: ...le mode version is available for longer distances potentially in excess of 15km The PRP ports support 100Base Fx using LC connectors Providing Ethernet redundancy the product can be described as a red...

Страница 18: ...and hence over both networks In an error free environment a second DANP receives the same packets on both interfaces possibly with a time delay between them The receiving DANP will use the first of t...

Страница 19: ...IGURE 3 SNMP MANAGEMENT The manager and agent use a Management Information Base MIB and a relatively small set of commands to exchange information The MIB is organised in a tree structure with individ...

Страница 20: ...4 sysContact user configurable 5 sysName SRP2xx user configurable 6 sysLocation user configurable 7 sysServices 2 3 3 2 H38x Interface MIB Structure Address Name 0 Ccitt 1 ISO 3 Org 6 DOD 1 Internet...

Страница 21: ...StatsOversizePkts 11 etherStatsFragments 12 etherStatsJabbers 13 etherStatsCollision 14 etherStatsPkts64Octets 15 etherStatsPkts65to127Octets 16 etherStatsPkts128to255Octets 17 etherStatsPkts256to511O...

Страница 22: ...kdown or authentication failure The version used is SNMP v1 and the traps are shown in the table below Trap Type Name Description 0 coldstart The switch is booting 1 warmstart The switch is rebooting...

Страница 23: ...ol for clock synchronisation between computer systems over packet switched variable latency data networks The switch can be synchronized by the NTP protocol as an NTP client 3 4 3 IRIG B A time synchr...

Страница 24: ...lains the allocation and meaning of these LEDs Allocation Meaning Port 3 Activity Port 2 Activity Port 1 Activity OFF no link ON good link Flashing activity on the link Heartbeat Flashes every second...

Страница 25: ...C Terminal 1 shows the state of Port A terminal 2 shows the state of Port B A closed contact indicates that the port is not working 3 5 3 TELNET Port A TELNET interface is used to configure set and in...

Страница 26: ...t Connector type Shielded RJ45 jack Twisted pair cable Cat 5 Max cable length with Cat 5 100 m TABLE 1 10 100BASETX PORT CHARACTERISTICS 4 3 2 100Base Fx Multimode Port Fibre port connector LC Optimal...

Страница 27: ...Ethernet Management Standards IEEE802 3 802 3u 802 3x Forwarding mode Store and forward Memory bandwidth 800 Mbps MAC Address 1K Address learning Automatic Illegal frame Dropped per 802 3 Late collisi...

Страница 28: ...connector Not applicable DM Copper Ethernet port Not applicable DM IRIG B connector Not applicable 4 6 1 2 Insulation resistance Standard IEC 60255 5 Note The test cannot be performed on the NC Normal...

Страница 29: ...tor Resistance 0 1 I 30A 2min NA Copper Ethernet port NA NA IRIG B connector NA 4 6 2 Electromagnetic compatibility 4 6 2 1 Electrostatic Discharge Standard IEEE 1613 ANSI IEEE C37 90 3 Application mo...

Страница 30: ...ernet port NA NA IRIG B connector NA 4 6 2 3 Electrical Fast Transient Burst immunity Standard IEC 61850 3 EN 61000 4 4 Application mode Group under test Test level CM Housing NA CM Power supply Class...

Страница 31: ...d disturbances immunity induced by radio frequency fields Standard IEC 61850 3 EN 61000 4 6 Application mode Group under test Test level NA Housing NA NA Power supply Class 3 10V 1kHz 80 am 150kHz to...

Страница 32: ...thernet port NA NA IRIG B connector NA 4 6 2 9 Conducted immunity common mode disturbance Standard IEC 61850 3 EN 61000 4 16 Application mode Group under test Test level CM Housing NA CM Power supply...

Страница 33: ...m contact Slow damped oscillatory wave Class 3 1kV 100kHz 2 5kV 1MHz Fast damped oscillatory wave Class 4 NA DM Earth connector NA DM Copper Ethernet port NA 4 6 2 11 Conducted emission limits Standar...

Страница 34: ...7 Application mode Group under test Test level DC Power supply Alternative component equal to 15 of the nominal DC voltage 4 6 3 3 Voltage dip immunity Standard IEC 60255 11 IEC 61000 4 29 Application...

Страница 35: ...ms i 1 2 In t 500 ms 4 6 3 9 Input current waveform limits Standard None Application mode Group under test Test level DC Power supply i peak to peak 10 In 4 6 4 AC auxiliary power supply 4 6 4 1 Volta...

Страница 36: ...25 C 96h Not energised Housing Test Ad 40 C 96h 4 6 5 2 Dry heat immunity Standard IEC 61850 3 IEEE 1613 IEC 60870 2 2 IEC 60068 2 2 Application mode Group under test Test level Energised Housing Tes...

Страница 37: ...es 4 6 6 3 Vibration response immunity Standard IEC 60255 21 1 Application mode Group under test Test level Energised Housing Class 2 1g 10 to 150Hz 1sweep cycles axis 4 6 6 4 Vibration endurance immu...

Страница 38: ...energised Housing Class 2 2g horizontal axis 7 5mm 1g vertical axis 3 5mm 4 6 7 Low Voltage Directive Standard EN 60950 1 Application mode Group under test Test level NA Housing 4 6 8 Degrees of prot...

Страница 39: ...ion H38x EN GL D11 DS Agile H38x Page 35 53 5 INSTALLATION This product is designed for mounting on a standard DIN Rail only The mounting brackets are shown in the figure below FIGURE 7 H38X DIN RAIL...

Страница 40: ...e earthed for safety reasons by connecting a protective conductor earth to a terminal which is marked with the protective earth symbol WARNING TO PRESERVE THE EQUIPMENT S SAFETY FEATURES THE PROTECTIV...

Страница 41: ...used for lower communication signals The screen is connected to the earth by two cable ends It is recommended to group the cables and link them together to the nearest earth plane or to an element of...

Страница 42: ...TED AS SHOWN IN THE FIGURE BELOW FIGURE 11 POWER SUPPLY WIRING The complete plastic cover must be fitted to the power supply connector as shown in the figure below The plastic cover must be secured wi...

Страница 43: ...ncy PRP ports with LC connectors It uses twisted pair cables for the Base Tx connections If Base Tx equipment is located at a long distance 100 m from the product or if the cables run through an elect...

Страница 44: ...THE SAFETY AND TECHNICAL DATA OF THE ALSTOM SAFETY GUIDE SFTY 4L M H11 OR LATER ISSUE AND THE RATINGS ON THE EQUIPMENT RATING LABEL YOU SHOULD ALSO READ THE SAFETY AND HANDLING SECTION OF THIS DOCUME...

Страница 45: ...Installing a replacement product To reinstall a replacement product 1 Fit the product to the DIN rail 2 Connect the protective earth connection 3 Connect the power supply connection s 4 Make a TELNET...

Страница 46: ...8 1 Login When the session is opened you will be have a login prompt and dialogue as shown in the figure below You login as either root or user initially with the password changeit Whilst the session...

Страница 47: ...s long in accordance with the standard Examples of the dialogue to set the passwords are given in the below 8 2 1 Setting the root administrator password setRootPassword Changing password for root New...

Страница 48: ...ip_addr setSnmpTrapIp 192 168 0 50 Set Synchronisation Mode setSyncrhoMode mode setSynchMode 0 Assigning the IP address and Subnet mask is the responsibility of the Network Manager A unique IP addres...

Страница 49: ...TransceiverADisable 0 En Disable Optical Transceiver B prpTransceiverBDisable 0 1 prpTransceiverADisable 0 Force a value 0 or 1 on the relay1 forceRelay1 0 1 forceRelay1 0 Force a value 0 or 1 on the...

Страница 50: ...000000 Late 00000000 Excessive 00000000 Multiple 00000000 Single 00000000 Deferred 00000000 InGoodOctet_l 00000000 InGoodOctet_h 00000000 InBadOctets 00000000 Hist64 00000000 Hist127 00000000 Hist255...

Страница 51: ...r A The command prpTransceiverBDisable 0 1 enables or disables optical transceiver B If set to 1 the port continues to receive data but does not transmit data If set to 0 the port is enable to transmi...

Страница 52: ...onfigured FTP server on a computer with a connection to the board and the IP address of the host as demonstrated in the figure below FTP FTP H38x FTP server S1035ENb Terminal Rootfs fffs2 Updatescript...

Страница 53: ...null null ftpget cmd USER anonymous ftpget cmd PASS ftpget cmd TYPE I null ftpget cmd PASV null ftpget cmd SIZE vmlinux bin ftpget cmd RETR vmlinux bin ftpget cmd null null ftpget cmd QUIT null Updati...

Страница 54: ...4 111 HDL version Version 2 0 Linux version 174 Tue Jul 31 16 40 44 CEST 2012 nios2 GNU Linux Current configuration is IP Add 192 168 0 22 Gateway IP Add 192 168 0 99 Netmask 255 255 255 0 MAC Add 80...

Страница 55: ...returns the proxy node table The proxy node table keeps track of peer PRP nodes The key attribute of the node table is the MAC address of the source node as received in the PRP supervision frame sent...

Страница 56: ...distance over which the signals can be transmitted and successfully received is affected by the optical loss as shown in the figure below FIGURE 17 FIBRE BUDGET For this product the optical budget is...

Страница 57: ...are address assigned to every network interface card Usually written in the form 01 23 45 67 89 ab MIB See Management Information Base in the Functional Description section NTP Network Time Protocol P...

Страница 58: ......

Страница 59: ...ct or will apply to any particular project This will depend on the technical and commercial circumstances It is provided without liability and is subject to change without notice Reproduction use or d...