122
Rockwell Automation Publication 520-UM002B-EN-E - December 2017
Chapter 7
Troubleshooting
When the drive enters a fault or
inhibit scenario, the fault
information will be shown and
scrolled across the LCD display.
Fault Codes
The fault code tables are designed to help you determine the source of the fault or
exception. When a fault condition is detected, the drive performs the appropriate
fault action, the fault is displayed, and the fault is added to a persistent fault log
(along with diagnostics data). The earlier faults have priority to be displayed.
The drive removes the fault text from the display when a Fault Reset service is
sent from the controller and the fault is no longer active. If a fault is still active
following a Fault Reset service, the fault is again posted to the display and written
to the fault log.
See
Troubleshoot the Safe Torque-Off Function on page 98
for information on
troubleshooting SAFE FLT fault codes.
Fault Code Summary
Fault Code Type
Description
FLT Sxx
Standard runtime axis exceptions.
FLT Mxx
INIT FLT Sxx
Exceptions that prevent normal operation and occur during the initialization process.
INIT FLT Mxx
INHIBIT Sxx
Exceptions that prevent normal operation and indicate whenever the drive is active.
INHIBIT Mxx
NODE FLTxx
Exceptions that prevent normal operation of the drive.
NODE ALARM xx
Exceptions that prevent normal operation of the drive, but do not result in any action other
than reporting the alarm to the controller.
TIP
Fault codes triggered by conditions that fall outside factory set limits are
identified by FL at the end of the display message. For example, FLT S07 – MTR
OVERLOAD FL.
Fault codes triggered by conditions that fall outside user set limits are
identified by UL at the end of the display message. For example, FLT S08 – MTR
OVERLOAD UL.
INIT FLT M12 INVALID FPGA REV
Fault type
Fault code
Fault description
FLT Sxx Fault Codes
Exception Code on Display
Exception Text
Problem
Possible Solutions
FLT S03 – MTR OVERSPEED FL
Motor Overspeed Factory Limit Fault
Motor speed has exceeded 590 Hz.
Check control loop tuning.
FLT S04 – MTR OVERSPEED UL
Motor Overspeed User Limit Fault
Motor speed has exceeded the user defined
speed limit given by Motor Overspeed User
Limit.
Check control loop tuning.
FLT S07 – MTR OVERLOAD FL
Motor Thermal Overload Factory Limit Fault The motor thermal model has exceeded its
factory set thermal capacity limit of 110%.
Modify the command profile to reduce speed
or increase time.
FLT S08 – MTR OVERLOAD UL
Motor Thermal Overload User Limit Fault
The motor thermal model has exceeded the
thermal capacity limit given by Motor
Thermal Overload User Limit.
•
Modify the command profile.
•
Increase the Motor Thermal Overload UL
attribute value.
Содержание PowerFlex 527
Страница 1: ...PowerFlex 527 Adjustable Frequency AC Drive Catalog Number 25C User Manual Original Instructions...
Страница 4: ...4 Rockwell Automation Publication520 UM002B EN E December 2017 Summary of Changes Notes...
Страница 8: ...8 Rockwell Automation Publication 520 UM002B EN E December 2017 Table of Contents Notes...
Страница 102: ...102 Rockwell Automation Publication520 UM002B EN E December 2017 Chapter 5 Hardwired Control of Safe Torque Off Notes...
Страница 162: ...162 Rockwell Automation Publication520 UM002B EN E December 2017 Appendix B Accessories and Dimensions Notes...
Страница 173: ...Rockwell Automation Publication520 UM002B EN E December 2017 173 Notes...
Страница 174: ...174 Rockwell Automation Publication 520 UM002B EN E December 2017 Notes...
Страница 175: ......