Rockwell Automation Publication 520-UM002B-EN-E - December 2017
127
Troubleshooting
Chapter 7
Fault Status Indicator
Condition
Safety Supervisor State
CIP Motion Axis State
Governing Object
Identity State
Steady Red
Any State
(1)
Aborting
Motion Axis
Major Recoverable or
Major Unrecoverable
Steady Red
Any State
(1)
Major Faulted
Motion Axis
Major Recoverable or
Major Unrecoverable
Steady Red
Abort
Any State
(1)
Safety Supervisor
Major Recoverable
Steady Red
Critical Fault
Any State
(1)
Safety Supervisor
Major Unrecoverable
(1) “Any State” means any state that has lower precedence.
Module Status Indicator
Condition
Safety Supervisor State
CIP Motion Axis State
Governing Object
Identity State
Flashing Green/Red
Self-Testing
Any State
(1)
Safety Supervisor
Device Self-Testing
Flashing Green/Red
Any State
(1)
Self-Testing
Motion Axis
Device Self-Testing
Steady Red
Self-Test Exception
Any State
(1)
Safety Supervisor
Major Unrecoverable
Flashing Green/Red
Waiting for TUNID
(2)
Any State
(1)
Safety Supervisor
Standby
Flashing Green/Red
Configuring
Any State
(1)
Safety Supervisor
Standby
Flashing Green
Idle
Any State
(1)
Safety Supervisor
Standby
Flashing Green
•
Waiting for TUNID with Torque
Permitted
(2)(3)
•
Executing
•
Executing with Torque
Permitted
(4)
•
Initializing
•
Pre-Charge
•
Shutdown
•
Start Inhibit
Motion Axis
Standby
Steady Green
•
Stopped
•
Stopping
•
Starting
•
Running
•
Testing
Motion Axis
Operational
Flashing Red or Steady Red
Any State
(1)
Aborting
Motion Axis
Major Recoverable or
Major Unrecoverable
Flashing Red
Any State
(1)
Major Faulted
Motion Axis
Major Recoverable or
Major Unrecoverable
Flashing Red
Abort
Any State
(1)
Safety Supervisor
Major Recoverable
Steady Red
Critical Fault
Any State
(1)
Safety Supervisor
Major Unrecoverable
(1) “Any State” means any state that has lower precedence.
(2) After Propose_TUNID service request, the Network Status indicator flashes Green/Red (fast flash) until successful Apply_TUNID.
(3) Unlike many Safety I/O devices, a CIP Motion Safety Drive is free to operate in its “Out of Box” state. This behavior is made explicit by the device specific Safety Supervisor state, Waiting for TUNID with
Torque Permitted. In this “Out of Box” state, operation of the CIP Motion Safety Drive is the same as that of a CIP Motion Drive to facilitate commissioning.
(4) Unlike many Safety I/O devices, a CIP Motion Safety Drive may be operated when the Safety Output assemblies Run/Idle bit is set to Idle. If in the Executing state, the Run/Idle bit is set to Idle, the device
is forced to a Safe State. However, if in this condition, the Safety Controller sends a Mode_Change service request with Torque Permitted to the Safety Stop Functions object, drive operation is permitted
while the Run/Idle bit remains Idle. See the Safety Stop Function object for details on the Mode_Change service.
Network Status Indicator
Condition
Status
Off
No power applied to the drive or IP address is not configured.
Flashing Green
Drive connection is not established, but has obtained an IP address.
Steady Green
Drive is online and has connections in the established state.
Flashing Red
One or more Exclusive Owner connections has timed out.
Steady Red
Duplicate IP address. IP address specified is already in use.
Flashing Green/Red (slow flash)
The drive performs self-test during powerup.
Flashing Green/Red (fast flash)
Safety Supervisor is waiting for “Apply TUNID” service request.
Содержание PowerFlex 527
Страница 1: ...PowerFlex 527 Adjustable Frequency AC Drive Catalog Number 25C User Manual Original Instructions...
Страница 4: ...4 Rockwell Automation Publication520 UM002B EN E December 2017 Summary of Changes Notes...
Страница 8: ...8 Rockwell Automation Publication 520 UM002B EN E December 2017 Table of Contents Notes...
Страница 102: ...102 Rockwell Automation Publication520 UM002B EN E December 2017 Chapter 5 Hardwired Control of Safe Torque Off Notes...
Страница 162: ...162 Rockwell Automation Publication520 UM002B EN E December 2017 Appendix B Accessories and Dimensions Notes...
Страница 173: ...Rockwell Automation Publication520 UM002B EN E December 2017 173 Notes...
Страница 174: ...174 Rockwell Automation Publication 520 UM002B EN E December 2017 Notes...
Страница 175: ......