Rockwell Automation Publication 520-UM002B-EN-E - December 2017
91
PowerFlex 527 Integrated Safe Torque-Off
Chapter 4
Out-of-Box (OOB) Safety
State
PowerFlex 527 drives ship in the out-of-box safety state.
Recognizing the Out-of-Box State
The safety control state can be read from the axis tag AxisSafetyState, or by using
a MSG command in Logix Designer software to read the Safety Supervisor
Status.
If the state is “Waiting for TUNID” (8) or “Waiting for TUNID with Torque
Permitted” (51) then the safety control is in the out-of-box state.
Restoring the Drive to the Out-of-Box State
After the integrated safety connection configuration is applied to the
PowerFlex 527 drive at least once, you can follow these steps to restore your
PowerFlex 527 drive to the out-of-box state.
1.
Right-click the PowerFlex 527 drive
you created, and choose Properties.
Safety Supervisor State: Values
Value
Definition
Definition
Mode
2
Idle
No active connections
Network
4
Executing
Normal running state
Network
7
Configuring
Transition state
Network
8
Waiting for TUNID
Out-of-Box state
Hardwired
51
Waiting for TUNID
with Torque Permitted
Out-of-Box state
Hardwired
52
Executing
with Torque Permitted
STO Bypass state
Network
Содержание PowerFlex 527
Страница 1: ...PowerFlex 527 Adjustable Frequency AC Drive Catalog Number 25C User Manual Original Instructions...
Страница 4: ...4 Rockwell Automation Publication520 UM002B EN E December 2017 Summary of Changes Notes...
Страница 8: ...8 Rockwell Automation Publication 520 UM002B EN E December 2017 Table of Contents Notes...
Страница 102: ...102 Rockwell Automation Publication520 UM002B EN E December 2017 Chapter 5 Hardwired Control of Safe Torque Off Notes...
Страница 162: ...162 Rockwell Automation Publication520 UM002B EN E December 2017 Appendix B Accessories and Dimensions Notes...
Страница 173: ...Rockwell Automation Publication520 UM002B EN E December 2017 173 Notes...
Страница 174: ...174 Rockwell Automation Publication 520 UM002B EN E December 2017 Notes...
Страница 175: ......