Rockwell Automation Publication 520-UM002B-EN-E - December 2017
31
Installation/Wiring
Chapter 1
an 85% coverage copper braided shield (with drain wire) surrounded by a
PVC jacket.
Other types of shielded cable are available, but the selection of these types may
limit the allowable cable length. Particularly, some of the newer cables twist 4
conductors of THHN wire and wrap them tightly with a foil shield. This
construction can greatly increase the cable charging current required and reduce
the overall drive performance. Unless specified in the individual distance tables as
tested with the drive, these cables are not recommended and their performance
against the lead length limits supplied is not known.
Reflected Wave Protection
The drive should be installed as close to the motor as possible. Installations with
long motor cables may require the addition of external devices to limit voltage
reflections at the motor (reflected wave phenomena). Refer to Reflected Wave in
“Wiring and Grounding Guide, (PWM) AC Drives,”
publication
The reflected wave data applies to all carrier frequencies 2...8 kHz.
Note:
For 240V ratings and lower, reflected wave effects do not need to be
considered.
Output Disconnect
The drive is intended to be commanded by motion commands that will start and
stop the motor. A device that routinely disconnects then reapplies output power
to the motor for the purpose of starting and stopping the motor should not be
used. If it is necessary to disconnect power to the motor with the drive outputting
power, use Logix Designer to disable the drive (Aux Fault or Coast to Stop).
Recommended Shielded Wire
Location
Rating/Type
Description
Standard (Option 1)
600V, 90
C (194
F) XHHW2/RHW-2
Anixter B209500-B209507, Belden
29501-29507, or equivalent
•
Four tinned copper conductors with XLPE insulation.
•
Copper braid/aluminum foil combination shield and
tinned copper drain wire.
•
PVC jacket.
Standard (Option 2)
Tray rated 600V, 90
C (194
F)
RHH/RHW-2 Anixter OLF-7xxxxx or
equivalent
•
Three tinned copper conductors with XLPE insulation.
•
5 mil single helical copper tape (25% overlap min.)
with three bare copper grounds in contact with shield.
•
PVC jacket.
Class I & II;
Division I & II
Tray rated 600V, 90
C (194
F)
RHH/RHW-2 Anixter 7V-7xxxx-3G or
equivalent
•
Three bare copper conductors with XLPE insulation
and impervious corrugated continuously welded
aluminum armor.
•
Black sunlight resistant PVC jacket overall.
•
Three copper grounds on #10 AWG and smaller.
Содержание PowerFlex 527
Страница 1: ...PowerFlex 527 Adjustable Frequency AC Drive Catalog Number 25C User Manual Original Instructions...
Страница 4: ...4 Rockwell Automation Publication520 UM002B EN E December 2017 Summary of Changes Notes...
Страница 8: ...8 Rockwell Automation Publication 520 UM002B EN E December 2017 Table of Contents Notes...
Страница 102: ...102 Rockwell Automation Publication520 UM002B EN E December 2017 Chapter 5 Hardwired Control of Safe Torque Off Notes...
Страница 162: ...162 Rockwell Automation Publication520 UM002B EN E December 2017 Appendix B Accessories and Dimensions Notes...
Страница 173: ...Rockwell Automation Publication520 UM002B EN E December 2017 173 Notes...
Страница 174: ...174 Rockwell Automation Publication 520 UM002B EN E December 2017 Notes...
Страница 175: ......