Rockwell Automation Publication 520-UM002B-EN-E - December 2017
105
Network Control of Safe Torque-Off
Chapter 6
The SI.ConnectionStatus tags indicate the status of the safety input connection.
Safe Torque-off Assembly Tags on page 105
lists the SAFETY tags added to the
controller tags when a PowerFlex 527 drive is added to a GuardLogix I/O
configuration and the connection is configured for “Motion and Safety” or for
“Safety only”.
The “Attribute” values listed are the Assembly Object attribute values.
STO Fault Reset
If a PowerFlex 527 drive safety control detects a fault, the input assembly tag
SI.SafetyFault is set to 1. A transition from logic 0 to 1 of the SO.Reset tag is
required after the SO.SafeTorqueOff tag has transitioned from logic 0 to 1.
To reset Axis.SafetyFault, a MAFR command must be issued.
Safe Torque-off Assembly Tags
Logix Designer Tag Name
Attribute
[bit]
Type
Description
SI.ConnectionStatus
(1),(2)
(1) Bits not listed are always zero.
(2) ConnectionStatus is determined by the Safety Validator in the GuardLogix controller.
DINT
SI.RunMode
[0]
BOOL
See Table 10 - Safety Connection Status in
GuardLogix Safety Reference Manual,
publication
SI.ConnectionFaulted
[1]
BOOL
SI.Status
(1),(3)
(3) The Status is sent from the drive to the controller using the CIP Safety protocol.
0x1A0
SINT
SI.TorqueDisabled
[0]
BOOL
0 = Torque Permitted; 1 = Torque Disabled
SI.SafetyFault
[6]
BOOL
1 = STO Fault present
SI.ResetRequired
[7]
BOOL
1 = A reset is required
SO.Command
(1),(4)
(4) The Command is sent from the controller to the drive using the CIP Safety protocol.
0x180
SINT
SO.SafeTorqueOff
[0]
BOOL
0 = Disable Permit; 1 = Permit Torque
SO.Reset
[7]
BOOL
0
→
1 = Reset STO Fault
ATTENTION:
Only data listed in
Safe Torque-off Assembly Tags on page 105
SAFETY data with SIL 3 integrity.
IMPORTANT
Transition of the SO.SafeTorqueOff tag to logic 1 must always be executed prior
to transition of the SO.Reset tag to logic 1.
IMPORTANT
PowerFlex 527 drives enter the STO Fault state if any STO function fault is
detected. Refer to
PowerFlex 527 Drive Troubleshooting on page 106
integrated safety troubleshooting.
Содержание PowerFlex 527
Страница 1: ...PowerFlex 527 Adjustable Frequency AC Drive Catalog Number 25C User Manual Original Instructions...
Страница 4: ...4 Rockwell Automation Publication520 UM002B EN E December 2017 Summary of Changes Notes...
Страница 8: ...8 Rockwell Automation Publication 520 UM002B EN E December 2017 Table of Contents Notes...
Страница 102: ...102 Rockwell Automation Publication520 UM002B EN E December 2017 Chapter 5 Hardwired Control of Safe Torque Off Notes...
Страница 162: ...162 Rockwell Automation Publication520 UM002B EN E December 2017 Appendix B Accessories and Dimensions Notes...
Страница 173: ...Rockwell Automation Publication520 UM002B EN E December 2017 173 Notes...
Страница 174: ...174 Rockwell Automation Publication 520 UM002B EN E December 2017 Notes...
Страница 175: ......