84
Rockwell Automation Publication 520-UM002B-EN-E - December 2017
Chapter 3
Configuring the PowerFlex 527 Drive with Integrated Motion
4.
In the Test Distance field, type 2.0 as the number of revolutions for the
test.
5.
Click the Motor Feedback tab.
6.
Click Start.
7.
Manually move the motor to the specific test distance. In this case, Step 4
dictated 2 revolutions
8.
Click the Motor and Feedback tab.
The Marker and Motor Feedback tests are not supported in Frequency
Control mode.
9.
Click Start.
The Logix Designer - Motor and Feedback Test dialog box appears. The
Test State is Executing. TESTING appears on the drive LCD display.
When the test completes successfully, the Test State changes from
Executing to Passed.
10.
Click OK.
This dialog box appears asking if the direction was correct.
11.
Click Yes.
Test
Description
Marker
Verifies marker detection capability as you rotate the motor shaft.
Motor Feedback
Verifies feedback connections are wired correctly as you rotate the motor shaft.
Motor and Feedback
Verifies motor power and feedback connections are wired correctly as you
command the motor to rotate.
Содержание PowerFlex 527
Страница 1: ...PowerFlex 527 Adjustable Frequency AC Drive Catalog Number 25C User Manual Original Instructions...
Страница 4: ...4 Rockwell Automation Publication520 UM002B EN E December 2017 Summary of Changes Notes...
Страница 8: ...8 Rockwell Automation Publication 520 UM002B EN E December 2017 Table of Contents Notes...
Страница 102: ...102 Rockwell Automation Publication520 UM002B EN E December 2017 Chapter 5 Hardwired Control of Safe Torque Off Notes...
Страница 162: ...162 Rockwell Automation Publication520 UM002B EN E December 2017 Appendix B Accessories and Dimensions Notes...
Страница 173: ...Rockwell Automation Publication520 UM002B EN E December 2017 173 Notes...
Страница 174: ...174 Rockwell Automation Publication 520 UM002B EN E December 2017 Notes...
Страница 175: ......