Rockwell Automation Publication 520-UM002B-EN-E - December 2017
Chapter 5
Hardwired Control of Safe Torque-Off
System Operation when Inputs are Meeting Timing Requirements
Troubleshoot the Safe Torque-Off Function
PowerFlex 527 Drive Troubleshooting
Event
Description
1
At least one input is switched off. GuardStopRequestStatus bit is set to 1.
2
Second input is switched off within 1 second. This must always occur within 1 second to prevent a
GuardStopInputFault condition.
3
First input is switched on.
4
Second input is switched on within 1 second of event 3.
5
Both inputs are in the ON state simultaneously within 1 second. As a result, the GuardStopInputFault is
not posted.
6
The GuardStopRequestStatus bit is set back to 0 if both inputs are in the ON state for 100 ms
continuously (100 ms debounce time).
(Safety Input) S1
1
3 4
5
6
Start Permit
OK
Permit Torque
Torque Permitted
Torque Permitted
(Safety Input) S2
GuardFault
SafeTorqueOffInhibit
GuardOKStatus
GuardGateDriveOutputStatus
GuardStopInputStatus
GuardStopRequestStatus
GuardStopInputFault
2
100 ms debounce time
1 second discrepancy limit
Start Inhibit
Torque Disabled
Disable Torque
No Fault
No Fault
Torque Disabled
Exception Code on Drive Display
Fault Message
Logix Designer
Problem
Possible Solutions
SAFE FLT 09 - SS IN
GuardStopInputFault
Safe torque-off function mismatch.
System does not allow motion. Safe
torque-off mismatch is detected
when safety inputs are in a different
state for more than 1.0 second.
•
Verify safety wiring and connections:
–
Wire terminations at safe torque-off
(STO) connector
–
Cable/header not seated correctly
–
+24V power
•
Check state of safety inputs.
•
Reset error and run proof test.
•
Return drive for repair if fault continues.
SAFE FLT S01 - SAFETY CORE
INTERNAL
CPUWatchdogFault
(1)
Drive safety diagnostic detected
internal STO design failure.
•
Cycle power.
•
Return drive for repair if fault continues.
SAFE FLT S03 - SAFE TORQUE OFF
SafeTorqueOffFault
(2)
Drive safety diagnostic detected
internal STO design failure.
•
Cycle power.
•
Execute STO function.
•
Return drive for repair if fault continues.
Hardwired safe torque off input
energized when drive is in network
safety mode.
Reset the drive to out-of-box settings,
hardwired safety mode. Refer to
the Drive to the Out-of-Box State on page 91
for instructions.
(1) Displayed in the LCD display as Module Fault.
(2) Displayed in the LCD display as Safety Fault.
Содержание PowerFlex 527
Страница 1: ...PowerFlex 527 Adjustable Frequency AC Drive Catalog Number 25C User Manual Original Instructions...
Страница 4: ...4 Rockwell Automation Publication520 UM002B EN E December 2017 Summary of Changes Notes...
Страница 8: ...8 Rockwell Automation Publication 520 UM002B EN E December 2017 Table of Contents Notes...
Страница 102: ...102 Rockwell Automation Publication520 UM002B EN E December 2017 Chapter 5 Hardwired Control of Safe Torque Off Notes...
Страница 162: ...162 Rockwell Automation Publication520 UM002B EN E December 2017 Appendix B Accessories and Dimensions Notes...
Страница 173: ...Rockwell Automation Publication520 UM002B EN E December 2017 173 Notes...
Страница 174: ...174 Rockwell Automation Publication 520 UM002B EN E December 2017 Notes...
Страница 175: ......