background image

 

A. 

If a roof vent is already present in the desired 

 

mounting location for the heat pump, the 

 

following steps must be taken. 

 

1.

 

Remove all screws which secure the roof 
vent to the vehicle.  Remove the vent and 
any additional trim materials.  Carefully 
remove all caulking from around the roof 
opening to obtain clean exterior roof 
surface. 

2.

 

It may be necessary to seal some of the old 
roof vent mounting screw holes which may 
fall outside of the heat pump basepan 
gasket. 

 

3.

 

Examine the roof opening.  If the opening is 
smaller than 356mm x 356mm, the opening 
must be enlarged. 

 
B. 

If a roof vent opening is not used, a new opening 

 

(See Figure 1) will have to be cut into the vehicle 

 

roof.  A matching opening will also have to be cut 

 

into the interior vehicle ceiling.  If the ceiling  

 

opening is carpeted, snagging could occur.  After the 

 

opening in the roof and interior ceiling are the correct 

 

size, a framed support structure must be provided 

 

between the exterior roof top and interior ceiling.   

 

The reinforced framed structure must provide the 

 

following guidelines: 

 

1.

 

Capable of supporting both the weight of 
the roof top heat pump and the interior 
ceiling assembly. 

 

2.

 

Capable of holding or supporting the roof 
outer surface and interior ceiling apart, so 
that when the roof top heat pump and 
ceiling assembly are bolted together, no 
collapsing occurs. 

 
 

Airxcel, Inc. recommends that the spacing from the 

 

vehicle roof top to the interior ceiling top be no less 

 

than 25mm.  A typical support frame is shown in 

 

Figure 1. 

 
 

 

 
 
 

 

 

The frame must provide an opening through the 

 

frame to allow passage for the power supply wiring. 

 

Route the supply wiring through the frame at the 

 

same time the support frame is being installed. 

 
C. 

The heat pump must be mounted as near level 

 

front to rear and side to side as possible when 
the vehicle is parked level.  Figure 2 shows the 
maximum allowable degree deviations. 
 
 

  

 

 

 

 
 
 
 
 
 
 
 
 
 

 

FIGURE 1 

 
 
IMPORTANT 

– Allow 600mm of supply wiring 

 

through the support frame (working length). 

 

After the support frame is installed, seal 

all gaps

 

 

between the frame and both the roof exterior and the 

 

supply wiring. 

 

 

 
 
 
 
 

FIGURE 2 

 

 

Содержание Coleman-Mach 47000 SERIES

Страница 1: ...N POUR 230 240 VCA 1 50 Hz S RIE 47000 POMPE CHALEUR ET CLIMATISEUR DE TOIT POUR V HICULE R CR ATIF INSTALLATIONSANLEITUNG F R 230 240 V Wechselspannung 1 50 Hz 47000er SERIE DACHKLIMAANLAGE W RMEPUMP...

Страница 2: ...HIS BOOKLET TO AVOID DAMAGE TO THE EQUIPMENT PERSONAL INJURY OR FIRE WARNING Improper installation may damage equipment can create a hazard and will void the warranty The use of components not tested...

Страница 3: ...ithout additional support structures Inspect the interior ceiling mounting area to avoid interference with existing structural members such as bunks curtains tracks or room dividers The depth of the c...

Страница 4: ...terior roof top and interior ceiling The reinforced framed structure must provide the following guidelines 1 Capable of supporting both the weight of the roof top heat pump and the interior ceiling as...

Страница 5: ...e Pull down all loose electrical connectors from the heat pump through the mounting opening and let hang V SECURING THE HEAT PUMP TO THE ROOF See Figure 4 A mounting frame is supplied with the ceiling...

Страница 6: ...6 FIGURE 4...

Страница 7: ...L POWER SUPPLY TO THE UNIT IS DISCONNECTED BEFORE PERFORMING ANY WORK ON THE UNIT TO AVOID THE POSSIBILITY OF SHOCK INJURY OR DAMAGE TO THE EQUIPMENT DANGER WITH NON METALLIC SHEATH CABLES ROMEX ETC S...

Страница 8: ...8 VII...

Страница 9: ...e air chute and allow the sensor to hang over the side of the chute Plug in the patch cord from the upper unit to the receptacle on the ceiling shroud as shown in the magnified section of Figure 6 F A...

Страница 10: ...10 FIGURE 6...

Страница 11: ...SCICULE AFIN D VITER LES RISQUES DE DOMMAGES L QUIPEMENT DE BLESSURES CORPORELLES OU D INCENDIE MISE EN GARDE L installation inappropri e peut endommager l quipement cr er un danger et annulera la gar...

Страница 12: ...fond afin d viter d interf rer avec des l ments structuraux tels que lits superpos s rideaux tringles rideaux ou s parations Le car nage de l ensemble de plafond est d une paisseur de 51 mm 2 po S ass...

Страница 13: ...ion maximum IMPORTANT Ins rer 600 mm de c blage d alimentation dans le cadre de support longueur utile Apr s l installation du cadre de support sceller tous les trous entre le cadre et l ext rieur du...

Страница 14: ...E DE D CHARGE LECTRIQUE AFIN D VITER TOUTE BLESSURE PAR D CHARGE LECTRIQUE ET TOUT DOMMAGE L QUIPEMENT CONFIRMER QUE TOUTES LES SOURCES D ALIMENTATION DE L UNIT SONT D BRANCH ES AVANT D ENTREPRENDRE Q...

Страница 15: ...centrale de la chute d air et laisser le capteur pendre sur le c t de la chute Brancher la fiche de connexion de l unit sup rieure la prise sur le car nage de l ensemble de plafond comme illustr dans...

Страница 16: ...LTIG UM SCH DEN AN DEN GER TEN PERSONENSCH DEN ODER BR NDE ZU VERMEIDEN WARNHINWEIS Eine nicht ordnungsgem e Installation kann eine Besch digung der Anlage nach sich ziehen eine Gefahr darstellen und...

Страница 17: ...Erw gung zu ziehen III AUSWAHL EINES INSTALLATIONSORTS Ihre Coleman Mach W rmepumpe ist prim r f r die Nutzung in Wohnmobilen ausgelegt Ist das Dach des Fahrzeugs f r Dachanlage und Deckeneinheit ohne...

Страница 18: ...2 F higkeit die Dachau enfl che und die Innendecke auseinanderzuhalten sodass diese bei Verschraubung von Dach W rmepumpe und Deckeneinheit nicht einknicken Airxcel Inc empfiehlt einen Abstand zwisch...

Страница 19: ...lastung f hren und an die Stromleiste anschlie en Schrauben mit einem Drehmoment von 8 kg cm anziehen Einige OEM Anlagen sind mit einer vorverdrahteten Stromversorgungsleitung mit Stecker ausgestattet...

Страница 20: ...des Luftkanals dr cken sodass der Sensor ber die Seite des Kanals berh ngen kann Das Verbindungskabel von der oberen Einheit in die Buchse an der Deckenblende wie im vergr erten Ausschnitt von Abbildu...

Страница 21: ...CENDIOS ADVERTENCIA La instalaci n incorrecta puede da ar el equipo puede crear una situaci n de riesgo y anular la garant a El uso de componentes que no hayan sido probados junto con estas unidades a...

Страница 22: ...ada para ser utilizada principalmente en casas rodantes Es el techo de su veh culo capaz de soportar tanto la unidad para techo como el ensamble del techo sin estructuras adicionales de soporte Inspe...

Страница 23: ...techo interior para que cuando la bomba de calor del techo exterior se emperne al ensamble del techo no se produzca ning n colapso Airxcel Inc recomienda que el espacio entre el techo exterior del veh...

Страница 24: ...s tornillos a un par de torsi n de 8 kg cm Algunas unidades del OEM est n equipadas con un cable de alimentaci n el ctrica cableado con anterioridad y con un enchufe con cerradura de resorte que encaj...

Страница 25: ...permita que el sensor cuelgue del lateral de la tolva Enchufe el cable de conexi n desde la parte superior de la unidad hasta el recept culo en la tapa del techo como se muestra en la secci n ampliada...

Страница 26: ...oducts Division Airxcel Inc RV Products Division P O Box 4020 Wichita KS 67204 Coleman is a registered trademark of The Coleman Company Inc used under license Mach is a registered trademark 1976B661 1...

Отзывы: