10.4.6.4
Verifying the re-trip mode
Choose the mode below, which corresponds to the actual case.
In the cases below it is assumed that
FunctionMode
=
Current
is selected.
Checking the case without re-trip,
RetripMode = Retrip Off
1.
Set
RetripMode
=
Retrip Off
.
2.
Apply the fault condition, including start of CCRBRF, well above the set current
value.
3.
Verify that no re-trip, but back-up trip is achieved after set time.
Checking the re-trip with current check,
RetripMode = CB Pos Check
1.
Set
RetripMode
=
CB Pos Check
.
2.
Apply the fault condition, including start of CCRBRF, well above the set current
value.
3.
Verify that re-trip is achieved after set time
t1
and back-up trip after time
t2
4.
Apply the fault condition, including the start of CCRBRF, with the current
below the set current value.
5.
Verify that no re-trip, and no back-up trip is obtained.
Checking re-trip without current check
1.
Set
RetripMode
=
No CBPos Check
.
2.
Apply the fault condition, including start of CCRBRF, well above the set current
value.
3.
Verify that re-trip is achieved after the set time
t1
, and the back-up trip after time
t2
.
4.
Apply the fault condition, including start of CCRBRF, with current below set
current value.
5.
Verify that re-trip is achieved after set time
t1
, but no back-up trip is obtained.
10.4.6.5
Verifying the back-up trip mode
In the cases below it is assumed that
FunctionMode
=
Current
is selected.
Checking that back-up tripping is not achieved at normal CB tripping
Use the actual tripping modes. The case below applies to re-trip with current check.
1.
Apply the fault condition, including start of CCRBRF, with phase current well
above set value
IP>
.
2.
Interrupt the current, with a margin before back-up trip time,
t2
. It may be made
at issue of re-trip command.
3.
Check that re-trip is achieved, if selected, but no back-up trip is obtained.
Section 10
1MRK 504 160-UEN -
Testing functionality by secondary injection
78
Transformer protection RET650 2.1 IEC
Commissioning manual
Содержание RET650 2.1 IEC
Страница 1: ...Relion 650 series Transformer protection RET650 2 1 IEC Commissioning manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 32: ...26 ...
Страница 48: ...42 ...
Страница 52: ...46 ...
Страница 72: ...66 ...
Страница 110: ...104 ...
Страница 116: ...110 ...
Страница 125: ...119 ...