Section 8
Establishing connection and verifying the
IEC 61850 communication
8.1
Overview
The rear OEM ports are used for:
•
station bus (IEC 61850-8-1) communication.
For IEC 61850-8-1 redundant communication, both rear OEM ports are utilized.
8.2
Setting the station communication
To enable IEC 61850 communication the corresponding OEM ports must be
activated. The rear OEM port AB and CD is used for IEC 61850-8-1 communication.
For IEC 61850-8-1 redundant communication, both OEM port AB and CD are used
exclusively.
To enable IEC 61850 station communication:
1.
Enable IEC 61850-8-1 (station bus) communication for port AB.
1.1. Set values for the rear ports AB.
Navigate to:
Main menu/Configuration/Communication/Ethernet
configuration/LANAB:1
Set values for
Mode
,
IPAddress
and
IPMask
.
Mode
must be set to
Normal
.
Check that the correct IP address is assigned to the port.
1.2. Enable IEC 61850-8-1 communication.
Navigate to:
Main menu/Configuration/Communication/Station
communication/IEC61850-8-1/IEC61850–8–1:1
Set
Operation
to
On
,
PortSelGOOSE
and
PortSelMMS
to the port used
(for example
LANAB
).
2.
Enable redundant IEC 61850-8-1 communication for port AB and CD
2.1. Enable redundant communication.
Navigate to:
Main menu/Configuration/Communication/Ethernet
configuration/PRP:1
Set values for
Operation
,
IPAddress
and
IPMask
.
Operation
must be set to
On
.
1MRK 504 160-UEN -
Section 8
Establishing connection and verifying the IEC 61850 communication
Transformer protection RET650 2.1 IEC
51
Commissioning manual
Содержание RET650 2.1 IEC
Страница 1: ...Relion 650 series Transformer protection RET650 2 1 IEC Commissioning manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 32: ...26 ...
Страница 48: ...42 ...
Страница 52: ...46 ...
Страница 72: ...66 ...
Страница 110: ...104 ...
Страница 116: ...110 ...
Страница 125: ...119 ...