Path in the local HMI under
Main menu/Configuration/Communication/SLM
configuration/Rear optical LON port
Table 12:
ADE Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation
TimerClass
Slow
Normal
Fast
-
-
Slow
Timer class
Path in the local HMI under
Main menu/Configuration/Communication/SLM
configuration/Rear optical LON port
Table 13:
LON commands
Command
Command description
ServicePinMsg
Command with confirmation. Transfers the node address to the LON Network Tool.
7.2
Optical budget calculation for serial communication
with LON
Table 14:
Example
Distance 1 km
Glass
Distance10 m
Plastic
Maximum attenuation
-11 dB
- 7 dB
4 dB/km multi mode: 820 nm - 62.5/125 um
4 dB
-
0.3 dB/m plastic: 620 nm - 1mm
-
3 dB
Margins for installation, aging, and so on
5 dB
2 dB
Losses in connection box, two contacts (0.75 dB/contact)
1.5 dB
-
Losses in connection box, two contacts (1dB/contact)
-
2 dB
Margin for repair splices (0.5 dB/splice)
0.5 dB
-
Maximum total attenuation
11 dB
7 dB
Section 7
1MRK 504 160-UEN -
Establishing connection and verifying the LON communication
50
Transformer protection RET650 2.1 IEC
Commissioning manual
Содержание RET650 2.1 IEC
Страница 1: ...Relion 650 series Transformer protection RET650 2 1 IEC Commissioning manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 32: ...26 ...
Страница 48: ...42 ...
Страница 52: ...46 ...
Страница 72: ...66 ...
Страница 110: ...104 ...
Страница 116: ...110 ...
Страница 125: ...119 ...