Bit A
Reg A
IEC 61850 name
SA name
Description
Values
550
386.06
.Str.phsB
Phase B Start
1 = Start
551
386.07
.Str.phsC
Phase C Start
1 = Start
552
386.08
.Op.general
Operate
General Operate
1 = Operate
553
386.09
.Op.phsA
Phase A Operate
1 = Operate
554
386.10
.Op.phsB
Phase B Operate
1 = Operate
555
386.11
.Op.phsC
Phase C Operate
1 = Operate
LD0.PHPTOC3
SIM8F-3/SIM4F-3
644
800.04
.Str.general
START
General Start
1 = Start
645
800.05
.Str.phsA
Phase A Start
1 = Start
646
800.06
.Str.phsB
Phase B Start
1 = Start
647
800.07
.Str.phsC
Phase C Start
1 = Start
648
800.08
.Op.general
Operate
General Operate
1 = Operate
649
800.09
.Op.phsA
Phase A Operate
1 = Operate
650
800.10
.Op.phsB
Phase B Operate
1 = Operate
651
800.11
.Op.phsC
Phase C Operate
1 = Operate
LD0.PHPTOC4
SIM8F-4/SIM4F-4
676
802.04
.Str.general
START
General Start
1 = Start
677
802.05
.Str.phsA
Phase A Start
1 = Start
678
802.06
.Str.phsB
Phase B Start
1 = Start
679
802.07
.Str.phsC
Phase C Start
1 = Start
680
802.08
.Op.general
Operate
General Operate
1 = Operate
681
802.09
.Op.phsA
Phase A Operate
1 = Operate
682
802.10
.Op.phsB
Phase B Operate
1 = Operate
683
802.11
.Op.phsC
Phase C Operate
1 = Operate
LD0.PHPTOC5
SIM8F-5/SIM4F-5
708
804.04
.Str.general
START
General Start
1 = Start
709
804.05
.Str.phsA
Phase A Start
1 = Start
710
804.06
.Str.phsB
Phase B Start
1 = Start
711
804.07
.Str.phsC
Phase C Start
1 = Start
712
804.08
.Op.general
Operate
General Operate
1 = Operate
713
804.09
.Op.phsA
Phase A Operate
1 = Operate
714
804.10
.Op.phsB
Phase B Operate
1 = Operate
715
804.11
.Op.phsC
Phase C Operate
1 = Operate
Section 7
1MRS757488 H
Modbus TCP communication
208
RIO600
Installation and Commissioning Manual
Содержание Remote I/O RIO600
Страница 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 14: ...6 ...
Страница 18: ...10 ...
Страница 64: ...56 ...
Страница 280: ...272 ...
Страница 306: ...298 ...
Страница 310: ...302 ...
Страница 311: ...303 ...