Operation principle
The
Operation
setting is used to enable or disable the function. The corresponding
parameter values are “On” and “Off”.
The operation of MFAPSDE can be described using a module diagram. All modules
in the diagram are explained in the next sections.
Multi-
frequency
admittance
calculation
MFAPSDE_ReEF
MFAPSDE_InEF
Io
Uo
General
fault
criterion
Fault
direction
determination
Operation
logic
Transient
detector
MFAPSDE_Oper
MFAPSDE_St
MFAPSDE_OpFw
MFAPSDE_OpRe
Timer
GUID-0E9EC3FB-FBC8-4BFA-92E9-F7FFC42AE956 V1 EN
Figure 69:
Functional module diagram
General fault criterion
The General fault criterion (GFC) module monitors the presence of earth fault in the
network and it is based on the value of the fundamental frequency zero-sequence
voltage defined as the vector sum of fundamental frequency phase voltage phasors
divided by three.
U
U
U
U
A
B
C
0
1
1
1
1
3
=
+
+
GUID-C4866966-64A3-4E7E-9794-8920040B61B5 V1 EN
(Equation 7)
When the magnitude of
U
0
1
exceeds the
Voltage start value
setting, an earth fault is
detected. The GFC module reports the exceeded value to the Fault direction
determination module and Operation logic. The reporting is referenced as General
Fault Criterion release.
Set the correct system phase-to-phase voltage with the
Nominal
Voltage
setting under the SIM8F operating parameter. The function
uses this value internally for calculation.
The
Voltage start value
setting defines the basic sensitivity of the MFAPSDE
function. To avoid unselective start or operation,
Voltage start value
must always be
set to a value which exceeds the maximum healthy state zero-sequence voltage value,
Section 6
1MRS757488 H
Commissioning
118
RIO600
Installation and Commissioning Manual
Содержание Remote I/O RIO600
Страница 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 14: ...6 ...
Страница 18: ...10 ...
Страница 64: ...56 ...
Страница 280: ...272 ...
Страница 306: ...298 ...
Страница 310: ...302 ...
Страница 311: ...303 ...