SCM8H / SCM8L
DI 1
DI 2
DI 3
DI 4
X1
0V-
DI1
DI2
DI3
DI4
0V-
1
2
3
4
5
6
X2
-
HS1
HS2
HS3
HS4
+
1
2
3
4
5
6
L-
L+
M
Disconnector CLOSE
Disconnector OPEN
COM for DI3 and DI4
HS1
HS2
HS3
HS4
GUID-B93E3F33-5A6E-42D1-9240-B9E860B0E4F0 V2 EN
Figure 29:
Connection diagram for two-position disconnector switch application
(rod type with DC motor)
Table 17:
SCM connection for two-position disconnector switch application
X1
Connector
inputs
Description
X2
Connector
outputs
Description
OV-
1
Common
return for DI1
and DI2
-
1
AUX. DC
voltage L-
DI1
2
Digital input 1
HS1
2
DC motor
connection
DI2
3
Digital input 2
HS2
3
DC motor
connection
DI3
4
Disconnector
switch CLOSE
position signal
HS3
4
DC motor
connection
DI4
5
Disconnector
switch OPEN
position signal
HS4
5
DC motor
connection
OV-
6
Common
return for DI3
and DI4
+
6
AUX. DC
voltage L+
1MRS757488 H
Section 5
Installing
RIO600
51
Installation and Commissioning Manual
Содержание Remote I/O RIO600
Страница 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 14: ...6 ...
Страница 18: ...10 ...
Страница 64: ...56 ...
Страница 280: ...272 ...
Страница 306: ...298 ...
Страница 310: ...302 ...
Страница 311: ...303 ...