Table 90:
SEQSPV Output signals
Name
Type
Description
FUSEF_U
BOOLEAN
General start of function
Settings
Table 91:
SEQSPVC Settings
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off/On
Neg Seq Current
Lev
4…1000
A
1
12
Operate level of neg
seq undercurrent
element
Neg Seq Voltage
Lev
300…10000
V
5
1500
Operate level of neg
seq overvoltage
element
Current Change
Rate
4…1000
A
1
60
Operate level of
change in phase
current
Voltage Change
Rate
300…10000
V
5
6000
Operate level of
change in phase
voltage
Change Rate
Enable
FALSE
TRUE
-
-
FALSE
Enabling operation
of change based
function
Min Op Voltage
Delta
300…10000
V
5
7500
Minimum operate
level of phase
voltage for delta
calculation
Min Op Current
Delta
4…1000
A
1
40
Minimum operate
level of phase
current for delta
calculation
Seal in Voltage
300…10000
V
5
7500
Operate level of
seal-in phase
voltage
Enable Seal In
FALSE
TRUE
-
-
FALSE
Enabling seal in
functionality
Current Dead Lin Val 4…1000
A
1
20
Operate level for
open phase current
detection
Table 92:
SEQSPVC Technical data
Characteristic
Value
Operate time accuracy
Depending on the nominal frequency of the
current measured: f
n
NPS function:
<36 ms for U
Fault
= 1.1 × set value
<22 ms for U
Fault
= 5 × set value
Delta function:
<34 ms for ΔU = 1.1 × set value
<28 ms for ΔU = 5 × set value
1MRS757488 H
Section 6
Commissioning
RIO600
143
Installation and Commissioning Manual
Содержание Remote I/O RIO600
Страница 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 14: ...6 ...
Страница 18: ...10 ...
Страница 64: ...56 ...
Страница 280: ...272 ...
Страница 306: ...298 ...
Страница 310: ...302 ...
Страница 311: ...303 ...