Table 111:
TCSHSCBR/TCSLSCBR Technical data
Characteristic
Value
Operate time accuracy
±1.0% of the set value or ±20 ms
6.2
Test mode handling
Use PCM600 to set the device in test mode.
In the test mode, RIO600 publishes GOOSE messages with the test bit activated (bit
11 of quality byte, as per IEC 61850
‐
8
‐
1) in the quality data attribute of the
corresponding data object. If RIO600 is configured for IEC 61850 Edition 1, the
global test bit in the GOOSE frame header is also set to “TRUE”.
RIO600 detects the test bit in the received message and operates the output for the
subscribed GOOSE messages.
Table 112:
Test mode operation
Test mode in subscriber RIO600 Test mode in publisher IED
Output contact on subscriber
RIO600 according to received
data
Off
Off
Operate
On
Off
Not operate
Off
On
Not operate
On
On
Operate
When RIO600 is in the test mode, the Ready LED of the LECM module flashes.
RIO600 does not support Simulation mode of IEC61850 Edition 2.
6.3
Channel output value handling
The channel values of the binary output modules follow the value in the subscribed
GOOSE message if the output is connected to the subscribed data. In case of
communication disturbances such as a broken Ethernet cable or GOOSE timeout, the
output values are restored to default, that is, set to failsafe values. When designing the
application, the failsafe value is “0” as the outputs are normally open contacts (NO).
For example, the blocking signals are enabled and the interlocking is released in the
failsafe state. Also, when RIO600 is powered off, the outputs go to the normal state,
which is open (“0”).
1MRS757488 H
Section 6
Commissioning
RIO600
167
Installation and Commissioning Manual
Содержание Remote I/O RIO600
Страница 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 14: ...6 ...
Страница 18: ...10 ...
Страница 64: ...56 ...
Страница 280: ...272 ...
Страница 306: ...298 ...
Страница 310: ...302 ...
Страница 311: ...303 ...