Section 11
Device and functionality tests
Table 202:
Inspection of mechanical structure
Description
Reference
Result
Markings and mechanical
structure
IEC 60255-1 and IEC 60255-27 OK
Enclosure class of the flush-
mounted device
IEC 60529
IP 20
Clearances and creepage
distances
IEC 60255-27
OK
Table 203:
Overload test
Description
Reference
Result
Thermal withstand capability
test
IEC 60255-1 and IEC 60255-27
OK
Table 204:
Power supply module tests
Test
Type test value
Result
Operating range of auxiliary
supply voltage test
80% and 120% of rated value for
DC
85% and 110% of rated value for
AC, frequency is between 50 Hz
for -5% and 60 Hz for +5%
IEC 60255-1 and IEEE
C37.90-2005
Power consumption of auxiliary
supply
IEC 60255-1 and IEEE
C37.90-2005
•
Quiescent load
<4 W
•
Maximum load
<12 W
Reversal of DC power supply
polarity
1 min for each polarity
IEC60255-27
Start-up time test
<30 s
1MRS757488 H