Bit A
Reg A
IEC 61850 name
SA name
Description
Values
2510
1568.14
<reserved>
<reserved>
2511
1568.15
OPEN_CB
Circuit Breaker Open
Command
0/1 = Off/On
2512
1569.00
CLOSE_CB
Circuit breaker Close
Command
0/1 = Off/On
2513
1569.01
<reserved>
<reserved>
1)
1. LD0.SCMLGGIO2/
LD0.SCMHGGIO2
2. LD0.SCMLPGGIO2/
LD0.SCMHPGGIO2
3. LD0.SCMLDGGIO2/
LD0.SCMHDGGIO2
4. LD0.SCMLEGGIO2/
LD0.SCMHEGGIO2
5. LD0.SCMLCGGIO2/
LD0.SCMHCGGIO2
SCM-2
2528
1570.00
.SPCSO1.stVal
Digital Output Channel 1
0/1 = Off/On
2529
1570.01
.SPCSO2.stVal
Digital Output Channel 2
0/1 = Off/On
2530
1570.02
.SPCSO3.stVal
Digital Output Channel 3
0/1 = Off/On
2531
1570.03
.SPCSO4.stVal
Digital Output Channel 4
0/1 = Off/On
2532
1570.04
<reserved>
<reserved>
2533
1570.05
<reserved>
<reserved>
2534
1570.06
<reserved>
<reserved>
2535
1570.07
<reserved>
<reserved>
2536
1570.08
CLOSE_ES
Earth Switch Close Command
0/1 = Off/On
2537
1570.09
OPEN_ES
Earth Switch Open Command
0/1 = Off/On
2538
1570.10
CLOSE_DS
Disconnector Close Command
0/1 = Off/On
2539
1570.11
OPEN_DS
Disconnector Open Command
0/1 = Off/On
2540
1570.12
<reserved>
<reserved>
2541
1570.13
<reserved>
<reserved>
2542
1570.14
<reserved>
<reserved>
2543
1570.15
OPEN_CB
Circuit Breaker Open
Command
0/1 = Off/On
2544
1571.00
CLOSE_CB
Circuit breaker Close
Command
0/1 = Off/On
2545
1571.01
<reserved>
Digital Output Channel 1
1)
1. LD0.SCMLGGIO3/
LD0.SCMHGGIO3
2. LD0.SCMLPGGIO3/
LD0.SCMHPGGIO3
3. LD0.SCMLDGGIO3/
LD0.SCMHDGGIO3
4. LD0.SCMLEGGIO3/
LD0.SCMHEGGIO3
5. LD0.SCMLCGGIO3/
LD0.SCMHCGGIO3
SCM-3
2560
1572.00
.SPCSO1.stVal
Digital Output Channel 1
0/1 = Off/On
Table continues on next page
Section 7
1MRS757488 H
Modbus TCP communication
252
RIO600
Installation and Commissioning Manual
Содержание Remote I/O RIO600
Страница 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 14: ...6 ...
Страница 18: ...10 ...
Страница 64: ...56 ...
Страница 280: ...272 ...
Страница 306: ...298 ...
Страница 310: ...302 ...
Страница 311: ...303 ...