5.2.2
Connecting Ethernet cable
Check that the proper power supply and LECM modules are mounted on the DIN rail.
The LECM module is supplied with two end caps and end clamps which must be
mounted at both ends of the RIO600 stack.
The communication module works as a RIO600 main module and communicates with
different digital I/O modules over backplane for achieving functionality based on the
output activation commands received through the communication services.
1.
Connect the Ethernet cable to the LECM module in RIO600.
The RJ-45 cable type must be shielded twisted cable, CAT5e at minimum. The
fiber-optic cable must be multimode type with LC connector.
2.
Connect the other end of the cable to the IEC 61850 station bus through the
Ethernet switch.
Ensure that the fiber-optic cable is connected on both ends of the
device. Looking directly at the LC connector may damage eyes.
Change the default IP address of the LECM module by using the
Parameter Setting tool in PCM600.
Table 8:
Default settings of the LECM module
Setting
Value
IP
192.168.2.10
Subnet mask
255.255.255.0
Default gateway
192.168.2.1
Time Synch source
none
Technical key
RIO1
In case of incomplete settings, the push button switch on the LECM
module can be used to restore the default settings.
During a configuration mismatch when the power is on, the LECM
module communicates through the previously configured IP address.
5.2.3
Connecting binary input signals
Check that the proper power supply and LECM modules are mounted on the DIN rail.
Section 5
1MRS757488 H
Installing
36
RIO600
Installation and Commissioning Manual