Bit A
Reg A
IEC 61850 name
SA name
Description
Values
2702
1580.14
<reserved>
<reserved>
2703
1580.15
OPEN_CB
Circuit Breaker Open
Command
0/1 = Off/On
2704
1581.00
CLOSE_CB
Circuit breaker Close
Command
0/1 = Off/On
2705
1581.01
<reserved>
<reserved>
1)
1. LD0.SCMLGGIO8/
LD0.SCMHGGIO8
2. LD0.SCMLPGGIO8/
LD0.SCMHPGGIO8
3. LD0.SCMLDGGIO8/
LD0.SCMHDGGIO8
4. LD0.SCMLEGGIO8/
LD0.SCMHEGGIO8
5. LD0.SCMLCGGIO8/
LD0.SCMHCGGIO8
SCM-8
2720
1582.00
.SPCSO1.stVal
Digital Output Channel 1
0/1 = Off/On
2721
1582.01
.SPCSO2.stVal
Digital Output Channel 2
0/1 = Off/On
2722
1582.02
.SPCSO3.stVal
Digital Output Channel 3
0/1 = Off/On
2723
1582.03
.SPCSO4.stVal
Digital Output Channel 4
0/1 = Off/On
2724
1582.04
<reserved>
<reserved>
2725
1582.05
<reserved>
<reserved>
2726
1582.06
<reserved>
<reserved>
2727
1582.07
<reserved>
<reserved>
2728
1582.08
CLOSE_ES
Earth Switch Close Command
0/1 = Off/On
2729
1582.09
OPEN_ES
Earth Switch Open Command
0/1 = Off/On
2730
1582.10
CLOSE_DS
Disconnector Close Command
0/1 = Off/On
2731
1582.11
OPEN_DS
Disconnector Open Command
0/1 = Off/On
2732
1582.12
<reserved>
<reserved>
2733
1582.13
<reserved>
<reserved>
2734
1582.14
<reserved>
<reserved>
2735
1582.15
OPEN_CB
Circuit Breaker Open
Command
0/1 = Off/On
2736
1583.00
CLOSE_CB
Circuit breaker Close
Command
0/1 = Off/On
2737
1583.01
<reserved>
<reserved>
1)
1. LD0.SCMLGGIO9/
LD0.SCMHGGIO9
2. LD0.SCMLPGGIO9/
LD0.SCMHPGGIO9
3. LD0.SCMLDGGIO9/
LD0.SCMHDGGIO9
4. LD0.SCMLEGGIO9/
LD0.SCMHEGGIO9
5. LD0.SCMLCGGIO9/
LD0.SCMHCGGIO9
SCM-9
2752
1584.00
.SPCSO1.stVal
Digital Output Channel 1
0/1 = Off/On
Table continues on next page
Section 7
1MRS757488 H
Modbus TCP communication
256
RIO600
Installation and Commissioning Manual
Содержание Remote I/O RIO600
Страница 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 14: ...6 ...
Страница 18: ...10 ...
Страница 64: ...56 ...
Страница 280: ...272 ...
Страница 306: ...298 ...
Страница 310: ...302 ...
Страница 311: ...303 ...