Table 52:
CMSTA, VMSTA & PEMSTA Output signals
Name
Type
Description
AvAmpsA
REAL
Phase A average current
MaxAmpsA
REAL
Phase A peak current
AvVoltsA
REAL
Phase to earth voltage A -
average value
MaxVoltsA
REAL
Phase to earth voltage A - peak
value
AvAmpsB
REAL
Phase B average current
MaxAmpsB
REAL
Phase B peak current
AvVoltsB
REAL
Phase to earth voltage B -
average value
MaxVoltsB
REAL
Phase to earth voltage B - peak
value
AvAmpsC
REAL
Phase C average current
MaxAmpsC
REAL
Phase C peak current
AvVoltsC
REAL
Phase to earth voltage C -
average value
MaxVoltsC
REAL
Phase to earth voltage C - peak
value
AvAmpsI0
REAL
Average Residual current
Applicable if "Io signal sel" is
"Measured Io"
MaxAmpsI0
REAL
Peak Residual current -
Applicable if "Io signal sel" is
"Measured Io"
AvW
REAL
Average total Active power
MaxW
REAL
Peak total Active power
AvVAr
REAL
Average total reactive power
MaxVAr
REAL
Peak total reactive power
AvVA
REAL
Average total apparent power
MaxVA
REAL
Peak total apparent power
Settings
Table 53:
CMSTA, VMSTA, PEMSTA Settings
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off/On
Avg Cal Time
Interval
3 min
10 min
15 min
1 hour
2 hours
24 hours
-
-
1 hour
Time internal over
which average
current, voltage and
power are calculated
Peak Cal Time
Interval
1 day
1 week
1 month
1 year
-
-
1 day
Time internal over
which peak current,
voltage and power
are calculated
Section 6
1MRS757488 H
Commissioning
84
RIO600
Installation and Commissioning Manual
Содержание Remote I/O RIO600
Страница 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 14: ...6 ...
Страница 18: ...10 ...
Страница 64: ...56 ...
Страница 280: ...272 ...
Страница 306: ...298 ...
Страница 310: ...302 ...
Страница 311: ...303 ...