Table 21:
Operating parameter settings for DIM8H and DIM8L
Parameter name
Range
Unit
Default value
Description
Debounce Time
5...4095
ms
10
This parameter is the debounce time for the DIM8
module in ms.
Oscillation Upper Limit
2...63
Counts
63
This parameter is the oscillation suppression
upper limit.
The parameter value acts as the count for upper
limit.
Oscillation Suppression
Hysteresis
1...62
Counts
62
This parameter is the oscillation suppression
Hysteresis.
The parameter value acts as the count for
Hysteresis.
Oscillation Time
0...4095
ms
4095
This parameter is the oscillation suppression time
limit. The parameter value acts as the time
window for the oscillation detection in ms.
0 means that no oscillation suppression is active.
Description
Digital Input 1...8 User defined channel name not exceeding 30
characters
Channel 1 Inversion
Non-Inverted/Inverted
Non Inverted
channel 1 input type: non-inverted/inverted
Channel 2 Inversion
Non-Inverted/Inverted
Non Inverted
channel 2 input type: non-inverted/inverted
Channel 3 Inversion
Non-Inverted/Inverted
Non Inverted
channel 3 input type: non-inverted/inverted
Channel 4 Inversion
Non-Inverted/Inverted
Non Inverted
channel 4 input type: non-inverted/inverted
Channel 5 Inversion
Non-Inverted/Inverted
Non Inverted
channel 5 input type: non-inverted/inverted
Channel 6 Inversion
Non-Inverted/Inverted
Non Inverted
channel 6 input type: non-inverted/inverted
Channel 7 Inversion
Non-Inverted/Inverted
Non Inverted
channel 7 input type: non-inverted/inverted
Channel 8 Inversion
Non-Inverted/Inverted
Non Inverted
channel 8 input type: non-inverted/inverted
Input Channel 1 Enabled/
Disabled
Enabled/Disabled
Enabled
channel 1: enabled/disabled
Input Channel 2 Enabled/
Disabled
Enabled/Disabled
Enabled
channel 2 : enabled/disabled
Input Channel 3 Enabled/
Disabled
Enabled/Disabled
Enabled
channel 3: enabled/disabled
Input Channel 4 Enabled/
Disabled
Enabled/Disabled
Enabled
channel 4: enabled/disabled
Input Channel 5 Enabled/
Disabled
Enabled/Disabled
Enabled
channel 5: enabled/disabled
Input Channel 6 Enabled/
Disabled
Enabled/Disabled
Enabled
channel 6: enabled/disabled
Input Channel 7 Enabled/
Disabled
Enabled/Disabled
Enabled
channel 7: enabled/disabled
Input Channel 8 Enabled/
Disabled
Enabled/Disabled
Enabled
channel 8: enabled/disabled
6.1.2.1
Binary input debounce time (filter time)
The filter time eliminates debounces and short disturbances on a binary input. The
filter time is set for each binary input.
1MRS757488 H
Section 6
Commissioning
RIO600
59
Installation and Commissioning Manual
Содержание Remote I/O RIO600
Страница 1: ... Remote I O RIO600 Installation and Commissioning Manual ...
Страница 2: ......
Страница 8: ......
Страница 14: ...6 ...
Страница 18: ...10 ...
Страница 64: ...56 ...
Страница 280: ...272 ...
Страница 306: ...298 ...
Страница 310: ...302 ...
Страница 311: ...303 ...