Name
Type
Description
V1RANG
INTEGER
V1 Magnitude range
V1ANGL
REAL
U1 Angle
V2
REAL
U2 Amplitude
V2RANG
INTEGER
V2 Magnitude range
V2ANGL
REAL
U2 Angle
14.1.6.4
Settings
Table 367:
VMSQI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
3V0DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
3V0Min
0 - 2000000
V
1
0
Minimum value
3V0Max
0 - 2000000
V
1
318000
Maximum value
3V0RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
3V0LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is common
for all limits
3V0AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
V1DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
V1Min
0 - 2000000
V
1
0
Minimum value
V1Max
0 - 2000000
V
1
106000
Maximum value
V1RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
V1AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
V2DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
V2Min
0 - 2000000
V
1
0
Minimum value
V2Max
0 - 2000000
V
1
106000
Maximum value
V2RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
V2LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is common
for all limits
V2AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
1MRK 502 048-UUS A
Section 14
Monitoring
523
Technical manual
Содержание Relion
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual...
Страница 2: ......
Страница 44: ...38...
Страница 62: ...56...
Страница 68: ...62...
Страница 156: ...150...
Страница 198: ...192...
Страница 512: ...506...
Страница 644: ...638...
Страница 714: ...708...
Страница 777: ...771...