14.14.4
Signals
Table 414:
SPVNZBAT Input signals
Name
Type
Default
Description
V_BATT
REAL
0.00
Battery terminal voltage that has to be supervised
BLOCK
BOOLEAN
0
Blocks all the output signals of the function
Table 415:
SPVNZBAT Output signals
Name
Type
Description
AL_VLOW
BOOLEAN
Alarm when voltage has been below low limit for a set
time
AL_VHI
BOOLEAN
Alarm when voltage has exceeded high limit for a set
time
PU_VLOW
BOOLEAN
Pick up signal when battery voltage drops below lower
limit
PU_VHI
BOOLEAN
Pick up signal when battery voltage exceeds upper limit
14.14.5
Settings
Table 416:
SPVNZBAT Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Enabled
Disable/Enable Operation
RtdBattVolt
20.00 - 250.00
V
1.00
110.00
Battery rated voltage
BattVoltLowLim
60 - 140
%Vbat
1
70
Lower limit for the battery terminal voltage
BattVoltHiLim
60 - 140
%Vbat
1
120
Upper limit for the battery terminal voltage
tDelay
0.000 - 60.000
s
0.001
0.200
Delay time for alarm
tReset
0.000 - 60.000
s
0.001
0.000
Time delay for reset of alarm
14.14.6
Measured values
Table 417:
SPVNZBAT Measured values
Name
Type
Default
Description
V_BATT
REAL
0.00
Battery terminal voltage that has to be supervised
BLOCK
BOOLEAN
0
Blocks all the output signals of the function
Section 14
1MRK 502 048-UUS A
Monitoring
594
Technical manual
Содержание Relion
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual...
Страница 2: ......
Страница 44: ...38...
Страница 62: ...56...
Страница 68: ...62...
Страница 156: ...150...
Страница 198: ...192...
Страница 512: ...506...
Страница 644: ...638...
Страница 714: ...708...
Страница 777: ...771...