Name
Values (Range)
Unit
Step
Default
Description
Z2Rev
0.005 - 3000.000
ohm/p
0.001
30.000
Reverse reach setting for Zone 2
tZ2
0.000 - 60.000
s
0.001
0.500
Time delay to operate for Zone 2
OpModeZ3
Disable-Zone
Enable-Zone
-
-
Disable-Zone
Operation mode of Zone 3
Z3Fwd
0.005 - 3000.000
ohm/p
0.001
30.000
Forward reach setting for Zone 3
Z3Rev
0.005 - 3000.000
ohm/p
0.001
30.000
Reverse reach setting for Zone 3
tZ3
0.000 - 60.000
s
0.001
1.000
Time delay to operate for Zone 3
Table 59:
ZGCPDIS (21G) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
LoadEnchModeZ3
Disabled
Enabled
-
-
Disabled
Enable load enchroachment mode Zone 3
Table 60:
ZGCPDIS (21G) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
7.2.6
Operation principle
7.2.6.1
Full scheme measurement
The execution of the different fault loops for phase-to-phase faults are executed in
parallel. The use of full scheme technique gives faster operation time compared to the
switched schemes that uses a pickup element to select correct voltage and current
depending on the fault type.
7.2.6.2
Impedance characteristic
The distance function consists of three zones. Each zone is self polarized offset mho
characteristics with reverse offset. The operating characteristic is in accordance to figure
Section 7
1MRK 502 048-UUS A
Impedance protection
162
Technical manual
Содержание Relion
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual...
Страница 2: ......
Страница 44: ...38...
Страница 62: ...56...
Страница 68: ...62...
Страница 156: ...150...
Страница 198: ...192...
Страница 512: ...506...
Страница 644: ...638...
Страница 714: ...708...
Страница 777: ...771...