When the apparent impedance reaches the zone Z2 this zone will operate, normally with
a longer delay. The zone is related to the static stability of the generator.
LEXPDIS (40) protection also has a directional blinder (supervision). See figure
.
In LEXPDIS (40) function the zone measurement is done as shown in figure
R
Offset
Z1 or Z2
XoffsetZ1
Z1diameter
Z (apparent impedance)
Z1 = Z - (Xof
Z1diameter/2)
en06000456-2.vsd
IEC06000456 V2 EN
Figure 72:
Zone measurement in LEXPDIS (40) protection function
The impedance Z1 is constructed from the measured apparent impedance Z and the
impedance corresponding to the centre point of the impedance characteristic (Z1 or Z2).
If the magnitude of this impedance is less than the radius (diameter/2) of the characteristic,
this part of the protection will operate.
If the directional restrain is set Disabled the impedance zone operation will start the
appropriate timer and LEXPDIS (40) will trip after the set delay (
tZ1
or
tZ2
).
If the directional restrain is set Enabled the directional release function must also operate
to enable operation. A new impedance is constructed from the measured apparent
impedance Z and the
XoffsetDirLine
point on the y-axis. If the phase angle of this
impedance is less than the set
DirAngle
LEXPDIS (40) function will be released, see
figure
.
1MRK 502 048-UUS A
Section 7
Impedance protection
171
Technical manual
Содержание Relion
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual...
Страница 2: ......
Страница 44: ...38...
Страница 62: ...56...
Страница 68: ...62...
Страница 156: ...150...
Страница 198: ...192...
Страница 512: ...506...
Страница 644: ...638...
Страница 714: ...708...
Страница 777: ...771...