10.2.3
Function block
ANSI09000280-1-en.vsd
SAPTOF (81)
V3P*
BLOCK
TRIP
BFI
BLKDMAGN
ANSI09000280 V1 EN
Figure 151:
SAPTOF (81) function block
10.2.4
Signals
Table 189:
SAPTOF (81) Input signals
Name
Type
Default
Description
V3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
Table 190:
SAPTOF (81) Output signals
Name
Type
Description
TRIP
BOOLEAN
Common trip signal
BFI
BOOLEAN
General pickup signal
BLKDMAGN
BOOLEAN
Measurement blocked due to low amplitude
10.2.5
Settings
Table 191:
SAPTOF (81) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disable / Enable
PUFrequency
35.00 - 75.00
Hz
0.01
51.20
Frequency set value
tDelay
0.000 - 60.000
s
0.001
0.200
Operate time delay
10.2.6
Monitored data
Table 192:
SAPTOF (81) Monitored data
Name
Type
Values (Range)
Unit
Description
FREQ
REAL
-
Hz
Measured frequency
Section 10
1MRK 502 048-UUS A
Frequency protection
324
Technical manual
Содержание Relion
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual...
Страница 2: ......
Страница 44: ...38...
Страница 62: ...56...
Страница 68: ...62...
Страница 156: ...150...
Страница 198: ...192...
Страница 512: ...506...
Страница 644: ...638...
Страница 714: ...708...
Страница 777: ...771...