14.1.7
Phase-neutral voltage measurement VNMMXU
14.1.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Phase-neutral voltage measurement
VNMMXU
U
SYMBOL-UU V1 EN
-
14.1.7.2
Function block
The available function blocks of an IED are depending on the actual hardware (TRM) and
the logic configuration made in PCM600.
ANSI08000226-1-en.vsd
VNMMXU
V3P*
V_A
VA_RANGE
VA_ANGL
V_B
VB_RANGE
VB_ANGL
V_C
VC_RANGE
VC_ANGL
ANSI08000226 V1 EN
Figure 240:
VNMMXU function block
14.1.7.3
Signals
Table 370:
VNMMXU Input signals
Name
Type
Default
Description
V3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
Table 371:
VNMMXU Output signals
Name
Type
Description
V_A
REAL
V_A Amplitude, magnitude of reported value
VA_RANGE
INTEGER
V_A Amplitude range
VA_ANGL
REAL
V_A Angle, magnitude of reported value
V_B
REAL
V_B Amplitude, magnitude of reported value
Table continues on next page
1MRK 502 048-UUS A
Section 14
Monitoring
525
Technical manual
Содержание Relion
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual...
Страница 2: ......
Страница 44: ...38...
Страница 62: ...56...
Страница 68: ...62...
Страница 156: ...150...
Страница 198: ...192...
Страница 512: ...506...
Страница 644: ...638...
Страница 714: ...708...
Страница 777: ...771...