9.3.5
Settings
Table 168:
ROV2PTOV (59N) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
OperationStep1
Disabled
Enabled
-
-
Enabled
Enable execution of step 1
Characterist1
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
-
-
Definite time
Selection of time delay curve type for step 1
Pickup1
1 - 200
%VB
1
30
Voltage start value (DT & IDMT) in % of VBase
for step 1
t1
0.00 - 6000.00
s
0.01
5.00
Definite time delay of step 1
t1Min
0.000 - 60.000
s
0.001
5.000
Minimum operate time for inverse curves for
step 1
TD1
0.05 - 1.10
-
0.01
0.05
Time multiplier for the inverse time delay for
step 1
OperationStep2
Disabled
Enabled
-
-
Enabled
Enable execution of step 2
Pickup2
1 - 100
%VB
1
45
Voltage start value (DT & IDMT) in % of VBase
for step 2
t2
0.000 - 60.000
s
0.001
5.000
Definite time delay of step 2
Table 169:
ROV2PTOV (59N) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
9.3.6
Monitored data
Table 170:
ROV2PTOV (59N) Monitored data
Name
Type
Values (Range)
Unit
Description
VLevel
REAL
-
kV
Magnitude of measured
voltage
9.3.7
Operation principle
Two step residual overvoltage protection ROV2PTOV (59N) is used to detect ground
(zero sequence) overvoltages. The ground overvoltage 3V
0
is normally computed by
Section 9
1MRK 502 048-UUS A
Voltage protection
296
Technical manual
Содержание Relion
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual...
Страница 2: ......
Страница 44: ...38...
Страница 62: ...56...
Страница 68: ...62...
Страница 156: ...150...
Страница 198: ...192...
Страница 512: ...506...
Страница 644: ...638...
Страница 714: ...708...
Страница 777: ...771...