have corresponding primary quantity, the 1:1 ratio shall be set for the used analogue
inputs on the IED, For example, HZPDIF.
•
Parameter IBase used by the tested function is set equal to the rated CT primary
current.
•
Parameter UBase used by the tested function is set equal to the rated primary phase-
to-phase voltage.
•
Parameter SBase used by the tested function is set equal to sqrt(3)* IBase* UBase for
three-phase power system.
3.4
Settings
Dependent on ordered IED type.
Table 1:
AISVBAS Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
PhaseAngleRef
TRM - Channel 1
TRM - Channel 2
TRM - Channel 3
TRM - Channel 4
TRM - Channel 5
TRM - Channel 6
TRM - Channel 7
TRM - Channel 8
TRM - Channel 9
TRM - Channel 10
AIM - Channel 1
AIM - Channel 2
AIM - Channel 3
AIM - Channel 4
AIM - Channel 5
AIM - Channel 6
AIM - Channel 7
AIM - Channel 8
AIM - Channel 9
AIM - Channel 10
-
-
TRM - Channel 1
Reference channel for phase angle
presentation
Table 2:
TRM_6I_4U Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CTStarPoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim1
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
Table continues on next page
1MRK 502 048-UUS A
Section 3
Analog inputs
49
Technical manual
Содержание Relion
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual...
Страница 2: ......
Страница 44: ...38...
Страница 62: ...56...
Страница 68: ...62...
Страница 156: ...150...
Страница 198: ...192...
Страница 512: ...506...
Страница 644: ...638...
Страница 714: ...708...
Страница 777: ...771...