
The binary input
BLOCK
can be used to block the function. The activation of the
BLOCK
input deactivates all outputs and resets internal timers. The alarm signals from the function
can be blocked by activating the binary input
BLK_ALM
.
14.17.8
Technical data
Table 432:
SSCBR Technical data
Function
Range or value
Accuracy
Alarm levels for open and close
travel time
(0-200) ms
± 0.5% ± 25 ms
Alarm levels for number of
operations
(0 - 9999)
-
Setting of alarm for spring
charging time
(0.00-60.00) s
± 0.5% ± 25 ms
Time delay for gas pressure alarm (0.00-60.00) s
± 0.5% ± 25 ms
Time delay for gas pressure
lockout
(0.00-60.00) s
± 0.5% ± 25 ms
14.18
Measurands for IEC 60870-5-103 I103MEAS
14.18.1
Functionality
103MEAS is a function block that reports all valid measuring types depending on
connected signals.
The measurand reporting interval set for MMXU function blocks, using the
xDbRepInt
and
xAngDbRepInt
settings, must be coordinated with the event reporting interval set for
the IEC 60870-5-103 communication using setting
CycMeasRepTime
.
Section 14
1MRK 502 048-UUS A
Monitoring
616
Technical manual
Содержание Relion
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual...
Страница 2: ......
Страница 44: ...38...
Страница 62: ...56...
Страница 68: ...62...
Страница 156: ...150...
Страница 198: ...192...
Страница 512: ...506...
Страница 644: ...638...
Страница 714: ...708...
Страница 777: ...771...